49
13 Protection Control
13.1. Restart Control (Time Delay Safety Control)
•
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2. 7 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
13.3. 60 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
•
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
13.4. Starting current Control
•
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
•
The reason of the difference is to reduce the starting current flow.
13.5. Freeze Preventive Control
• If the temperature of the indoor heat exchanger falls below 2
°
C continuously for 4 minutes or more, the compressor turns off. The
fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid from
returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10
°
C (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
Summary of Contents for CS-PC12MKF
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 11: ...11 5 Dimensions 5 1 Indoor Unit 5 1 1 CS PC12MKF ...
Page 12: ...12 5 1 2 CS PC18MKF CS PC24MKF ...
Page 13: ...13 5 2 Outdoor Unit 5 2 1 CU PC12MKF CU PC18MKF ...
Page 14: ...14 5 2 2 CU PC24MKF ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS PC12MKF ...
Page 17: ...17 7 2 CS PC18MKF CS PC24MKF ...
Page 21: ...21 9 Electronic Circuit Diagram 9 1 CS PC12MKF CU PC12MKF ...
Page 22: ...22 9 2 CS PC18MKF CU PC18MKF ...
Page 23: ...23 9 3 CS PC24MKF CU PC24MKF ...
Page 25: ...25 10 1 1 2 CS PC18MKF CS PC24MKF ...
Page 32: ...32 11 2 5 Wire Stripping And Connecting Requirement ...
Page 56: ...56 16 1 1 3 To remove Discharge Grille ...
Page 57: ...57 16 1 1 4 To remove Control Board 16 1 1 5 To remove Cross Flow Fan and Indoor Fan Motor ...
Page 58: ...58 ...
Page 60: ...60 16 2 1 3 To remove Discharge Grille ...
Page 61: ...61 16 2 1 4 To remove Control Board 16 2 1 5 To remove Cross Flow Fan and Indoor Fan Motor ...
Page 62: ...62 ...
Page 63: ...63 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...
Page 71: ...71 17 4 Cooling Capacity Performance Data CS CU PC12MKF 220V ...
Page 72: ...72 CS CU PC12MKF 240V CS CU PC18MKF 220V ...
Page 73: ...73 CS CU PC18MKF 240V ...
Page 74: ...74 CS CU PC24MKF 220V ...
Page 75: ...75 CS CU PC24MKF 240V ...
Page 76: ...76 17 5 Sound Data CS PC18MKF ...
Page 77: ...77 CS PC24MKF ...