12.9. Random Auto Restart Control
• If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when the power is
resumed.
• It will start with previous operation mode and airflow direction.
• If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to operate will be
decided randomly using 4 parameters:- intake air temperature, setting temperature, fan speed and air swing louver position.
• This Random Auto Restart Control is not available when Timer is set.
• This control can be omitted by open the circuit of JX02 (refer to printed circuit board indoor unit).
12.10. Remote Control Signal Receiving Sound
• Short beep sound will be heard when turn ON the air conditioner or enabling other operations.
• Long beep sound will be heard when turn OFF the air conditioner or disabling other operations.
Summary of Contents for CS-PC12MKF
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 11: ...11 5 Dimensions 5 1 Indoor Unit 5 1 1 CS PC12MKF ...
Page 12: ...12 5 1 2 CS PC18MKF CS PC24MKF ...
Page 13: ...13 5 2 Outdoor Unit 5 2 1 CU PC12MKF CU PC18MKF ...
Page 14: ...14 5 2 2 CU PC24MKF ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS PC12MKF ...
Page 17: ...17 7 2 CS PC18MKF CS PC24MKF ...
Page 21: ...21 9 Electronic Circuit Diagram 9 1 CS PC12MKF CU PC12MKF ...
Page 22: ...22 9 2 CS PC18MKF CU PC18MKF ...
Page 23: ...23 9 3 CS PC24MKF CU PC24MKF ...
Page 25: ...25 10 1 1 2 CS PC18MKF CS PC24MKF ...
Page 32: ...32 11 2 5 Wire Stripping And Connecting Requirement ...
Page 56: ...56 16 1 1 3 To remove Discharge Grille ...
Page 57: ...57 16 1 1 4 To remove Control Board 16 1 1 5 To remove Cross Flow Fan and Indoor Fan Motor ...
Page 58: ...58 ...
Page 60: ...60 16 2 1 3 To remove Discharge Grille ...
Page 61: ...61 16 2 1 4 To remove Control Board 16 2 1 5 To remove Cross Flow Fan and Indoor Fan Motor ...
Page 62: ...62 ...
Page 63: ...63 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...
Page 71: ...71 17 4 Cooling Capacity Performance Data CS CU PC12MKF 220V ...
Page 72: ...72 CS CU PC12MKF 240V CS CU PC18MKF 220V ...
Page 73: ...73 CS CU PC18MKF 240V ...
Page 74: ...74 CS CU PC24MKF 220V ...
Page 75: ...75 CS CU PC24MKF 240V ...
Page 76: ...76 17 5 Sound Data CS PC18MKF ...
Page 77: ...77 CS PC24MKF ...