12.2.1.5. Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
If compressor discharge temperature exceeds 110
°
C, compressor will stop, occurs 4 times per 20 minutes, timer LED will be
blinking. (“F97” is to be confirmed.)
12.2.1.6. Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.6A and 1.15A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4
°
C.
• During Heating operations :
Indoor piping temperature - indoor suction is under 5
°
C.
b. Control contents
• Compressor stops (and restart after 3 minutes).
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated.
12.2.1.7. Low Frequency Protection Control 1
When the compressor operates at frequency lower than 25 Hz continued for 240 minutes, the operation frequency will be changed
to 24 Hz for 2 minutes.
12.2.1.8. Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (
°
C)
T < 14 or T 30
T < 14 or T 28
Outdoor air (
°
C)
T < 13 or T 38
T < 4 or T 24
Indoor heat exchanger (
°
C)
T < 30
T
0
Summary of Contents for CS-HE12GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit ...
Page 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 17: ...17 9 2 Outdoor Unit ...
Page 19: ...19 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 20: ...20 ...
Page 27: ...27 4 Attach the control board cover back to the original position with the screw ...
Page 57: ...57 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS HE9GKE CU HE9GKE ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 16 1 2 CS HE12GKE CU HE12GKE ...
Page 62: ...62 ...
Page 63: ...63 ...
Page 64: ...64 ...