36
12.2. Protection Control
12.2.1.
Protection Control For All Operations
12.2.1.1. Time Delay Safety Control
1. The compressor will not starts for 3 minutes after stop of the operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
12.2.1.2. 30 Seconds Forced Operation
1. Once compressor starts the operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped with the remote control or the Auto Switch on the indoor unit.
12.2.1.3. Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
12.2.1.4. IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 100
°
C, compressor operation will stop immediately.
2. Compressor operation restarts after 3 minutes the temperature decreases to 95
°
C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 20.2 A, the compressor will stop operate. Then, operation will restart
after 3 minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 1
minute.
3. If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after 2 minutes. If
this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off.
Model
HE9GK
HE12GK
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
4.95
16.99
5.76
16.99
Cooling/Soft Dry (B)
4.43
16.99
5.24
16.99
Cooling/Soft Dry (C)
4.95
16.99
5.76
16.99
Heating
6.2
16.99
8.1
16.99
Summary of Contents for CS-HE12GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit ...
Page 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 17: ...17 9 2 Outdoor Unit ...
Page 19: ...19 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 20: ...20 ...
Page 27: ...27 4 Attach the control board cover back to the original position with the screw ...
Page 57: ...57 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS HE9GKE CU HE9GKE ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 16 1 2 CS HE12GKE CU HE12GKE ...
Page 62: ...62 ...
Page 63: ...63 ...
Page 64: ...64 ...