![Panasonic CS-E7JKEW Service Manual Download Page 81](http://html1.mh-extra.com/html/panasonic/cs-e7jkew/cs-e7jkew_service-manual_4188273081.webp)
81
H39
Abnormal indoor
operating unit or
standby units
3 times happen
within 40 minutes
—
Wrong wiring and connecting
pipe, expansion valve
abnormality, indoor heat
exchanger sensor open
circuit
• Check indoor/outdoor connection
wire and connection pipe
• Indoor heat exchanger sensor
lead wire and connector
• Expansion valve and lead wire
and connector
H41
Abnormal wiring or
piping connection
—
—
Wrong wiring and connecting
pipe, expansion valve
abnormality
• Check indoor/outdoor connection
wire and connection pipe
• Expansion valve and lead wire
and connector.
H58
Indoor gas sensor
abnormality
Continuous for 6
hours
—
Indoor gas sensor open or
short circuit
• Indoor gas sensor
• Indoor PCB
H64
Outdoor high pressure
sensor abnormality
Continuous for 1
minutes
—
High pressure sensor open
circuit during compressor
stop
• High pressure sensor
• Lead wire and connector
H97
Outdoor fan motor
mechanism lock
2 times happen
within 30 minutes
—
Outdoor fan motor lock or
feedback abnormal
• Outdoor fan motor lead wire and
connector
• Fan motor lock or block
H98
Indoor high pressure
protection
—
—
Indoor high pressure
protection (Heating)
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
H99
Indoor operating unit
freeze protection
—
—
Indoor freeze protection
(Cooling)
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
F11
4-way valve switching
abnormality
4 times happen
within 30 minutes
—
4-way valve switching
abnormal
• 4-way valve
• Lead wire and connector.
F17
Indoor standby units
freezing abnormality
3 times happen
within 40 minutes
—
Wrong wiring and connecting
pipe, expansion valve
leakage, indoor heat
exchanger sensor open
circuit
• Check indoor/outdoor connection
wire and pipe
• Indoor heat exchanger sensor
lead wire and connector
• Expansion valve lead wire and
connector.
F90
Power factor correction
(PFC) circuit protection
4 times happen
within 10 minutes
—
Power factor correction
circuit abnormal
• Outdoor PCB faulty
F91
Refrigeration cycle
abnormality
2 times happen
within 20 minutes
—
Refrigeration cycle abnormal
• Insufficient refrigerant or valve
close
F93
Compressor abnormal
revolution
4 times happen
within 20 minutes
—
Compressor abnormal
revolution
• Power transistor module faulty or
compressor lock
F94
Compressor discharge
pressure overshoot
protection
4 times happen
within 30 minutes
—
Compressor discharge
pressure overshoot
• Check refrigeration system
F95
Outdoor cooling high
pressure protection
4 times happen
within 20 minutes
—
Cooling high pressure
protection
• Check refrigeration system
• Outdoor air circuit
F96
Power transistor module
overheating protection
4 times happen
within 30 minutes
—
Power transistor module
overheat
• PCB faulty
• Outdoor air circuit (fan motor)
F97
Compressor
overheating protection
3 times happen
within 30 minutes
—
Compressor overheat
• Insufficient refrigerant
F98
Total running current
protection
3 times happen
within 20 minutes
—
Total current protection
• Check refrigeration system
• Power source or compressor lock
F99
Outdoor direct current
(DC) peak detection
Continuous
happen for 7 times
—
Power transistor module
current protection
• Power transistor module faulty or
compressor lock
Abnormality /
Protection control
Abnormality
Judgement
Protection
operation
Problem
Check location
Diagnosis
display
Summary of Contents for CS-E7JKEW
Page 21: ...21 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 27: ...27 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 30: ...30 6 Refrigeration Cycle Diagram 6 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 31: ...31 6 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 32: ...32 6 3 CU E15JKE ...
Page 33: ...33 7 Block Diagram 7 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 34: ...34 7 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 35: ...35 7 3 CU E15JKE ...
Page 36: ...36 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 38: ...38 8 2 2 CU E15JKE ...
Page 39: ...39 8 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 40: ...40 8 2 4 CU E15JKE 1 ...
Page 41: ...41 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 43: ...43 9 2 2 CU E15JKE ...
Page 44: ...44 9 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 45: ...45 9 2 4 CU E15JKE 1 ...
Page 46: ...46 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 47: ...47 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 49: ...49 10 2 Outdoor Unit 10 2 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 50: ...50 10 2 2 CU E15JKE ...
Page 51: ...51 10 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 113: ...113 17 1 3 To remove discharge grille ...
Page 114: ...114 17 1 4 To remove control board 17 1 5 To remove cross flow fan and indoor fan motor ...
Page 115: ...115 ...
Page 118: ...118 18 Technical Data 18 1 Operation Characteristics 18 1 1 CU E7JKE ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...121 ...
Page 122: ...122 18 1 2 CU E9JKE ...
Page 123: ...123 ...
Page 124: ...124 ...
Page 125: ...125 ...
Page 126: ...126 18 1 3 CU E12JKE ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 18 1 4 CU E15JKE ...
Page 131: ...131 ...
Page 132: ...132 ...
Page 133: ...133 ...
Page 134: ...134 18 1 5 CU E15JKE 1 ...
Page 135: ...135 ...
Page 136: ...136 ...
Page 137: ...137 ...
Page 138: ...138 18 1 6 CU E7JKE 3 ...
Page 139: ...139 ...
Page 140: ...140 ...
Page 141: ...141 ...
Page 142: ...142 18 1 7 CU E9JKE 3 ...
Page 143: ...143 ...
Page 144: ...144 ...
Page 145: ...145 ...
Page 146: ...146 18 1 8 CU E12JKE 3 ...
Page 147: ...147 ...
Page 148: ...148 ...
Page 149: ...149 ...