14 Protection Control
14.1. Protection Control For All Operations
14.1.1.
Restart Control (Time Delay Safety Control)
• The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by
pressing OFF/ON button at remote control within this period.
• This control is not applicable if the power supply is cut off and on again.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
14.1.2.
30 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON button at the remote control
is permitted or the Auto OFF/ON button at indoor unit.
• The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
14.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
14.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 100
°
C, compressor operation will stop immediately.
2. Compressor operation restarts after 3 minutes the temperature decreases to 95
°
C.
3. If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 18.5 A, the compressor will stop operate. Then, operation will restart
after 3 minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 2
minutes.
3. If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after 1 minute. If
this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer LED will be blinking (“F99”
is indicated).
Model
E7JK
E9JK
E12JK
E15JK-1
E15JKE
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
3.95
15.0
4.54
15.0
6.86
15.0
7.52
15.0
9.0
15.0
Cooling/Soft Dry (B)
3.6
15.0
4.12
15.0
6.35
15.0
7.16
15.0
8.5
15.0
Heating
4.37
15.0
5.57
15.0
8.03
15.0
8.55
15.0
9.8
15.0
Summary of Contents for CS-E7JKEW
Page 21: ...21 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 27: ...27 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 30: ...30 6 Refrigeration Cycle Diagram 6 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 31: ...31 6 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 32: ...32 6 3 CU E15JKE ...
Page 33: ...33 7 Block Diagram 7 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 34: ...34 7 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 35: ...35 7 3 CU E15JKE ...
Page 36: ...36 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 38: ...38 8 2 2 CU E15JKE ...
Page 39: ...39 8 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 40: ...40 8 2 4 CU E15JKE 1 ...
Page 41: ...41 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 43: ...43 9 2 2 CU E15JKE ...
Page 44: ...44 9 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 45: ...45 9 2 4 CU E15JKE 1 ...
Page 46: ...46 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 47: ...47 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 49: ...49 10 2 Outdoor Unit 10 2 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 50: ...50 10 2 2 CU E15JKE ...
Page 51: ...51 10 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 113: ...113 17 1 3 To remove discharge grille ...
Page 114: ...114 17 1 4 To remove control board 17 1 5 To remove cross flow fan and indoor fan motor ...
Page 115: ...115 ...
Page 118: ...118 18 Technical Data 18 1 Operation Characteristics 18 1 1 CU E7JKE ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...121 ...
Page 122: ...122 18 1 2 CU E9JKE ...
Page 123: ...123 ...
Page 124: ...124 ...
Page 125: ...125 ...
Page 126: ...126 18 1 3 CU E12JKE ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 18 1 4 CU E15JKE ...
Page 131: ...131 ...
Page 132: ...132 ...
Page 133: ...133 ...
Page 134: ...134 18 1 5 CU E15JKE 1 ...
Page 135: ...135 ...
Page 136: ...136 ...
Page 137: ...137 ...
Page 138: ...138 18 1 6 CU E7JKE 3 ...
Page 139: ...139 ...
Page 140: ...140 ...
Page 141: ...141 ...
Page 142: ...142 18 1 7 CU E9JKE 3 ...
Page 143: ...143 ...
Page 144: ...144 ...
Page 145: ...145 ...
Page 146: ...146 18 1 8 CU E12JKE 3 ...
Page 147: ...147 ...
Page 148: ...148 ...
Page 149: ...149 ...