57
11.3.3.
Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N
•
m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
11.3.4.
Connect the Cable to the Outdoor Unit
1. Remove the control board cover from the unit by
loosening the screw.
2. Cable connection to the power supply through Isolating
Devices (Disconnecting means).
• Connect approved type polychloroprene sheathed
power supply cord
3 x 1.5 mm
2
(3/4 ~ 1.75HP), 3 x 2.5
mm
2
(2.0 ~ 2.5HP) or 3 x 4.0 mm
2
(3.0HP) type
designation 245 IEC 57 or heavier cord to the terminal
board, and connect the others end of the cord to
Isolating Devices (Disconnecting means).
3.
Connecting cable
between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier
cord.
4. Connect the power supply cord and connecting cable
between indoor unit and outdoor unit according to the
diagram below.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step
above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step
.
- If the leak does not stop when the connections are retightened, repair the location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
Summary of Contents for CS-E7JKEW
Page 21: ...21 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 27: ...27 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 30: ...30 6 Refrigeration Cycle Diagram 6 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 31: ...31 6 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 32: ...32 6 3 CU E15JKE ...
Page 33: ...33 7 Block Diagram 7 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 34: ...34 7 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 35: ...35 7 3 CU E15JKE ...
Page 36: ...36 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 38: ...38 8 2 2 CU E15JKE ...
Page 39: ...39 8 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 40: ...40 8 2 4 CU E15JKE 1 ...
Page 41: ...41 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 43: ...43 9 2 2 CU E15JKE ...
Page 44: ...44 9 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 45: ...45 9 2 4 CU E15JKE 1 ...
Page 46: ...46 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 47: ...47 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 49: ...49 10 2 Outdoor Unit 10 2 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 50: ...50 10 2 2 CU E15JKE ...
Page 51: ...51 10 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 113: ...113 17 1 3 To remove discharge grille ...
Page 114: ...114 17 1 4 To remove control board 17 1 5 To remove cross flow fan and indoor fan motor ...
Page 115: ...115 ...
Page 118: ...118 18 Technical Data 18 1 Operation Characteristics 18 1 1 CU E7JKE ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...121 ...
Page 122: ...122 18 1 2 CU E9JKE ...
Page 123: ...123 ...
Page 124: ...124 ...
Page 125: ...125 ...
Page 126: ...126 18 1 3 CU E12JKE ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 18 1 4 CU E15JKE ...
Page 131: ...131 ...
Page 132: ...132 ...
Page 133: ...133 ...
Page 134: ...134 18 1 5 CU E15JKE 1 ...
Page 135: ...135 ...
Page 136: ...136 ...
Page 137: ...137 ...
Page 138: ...138 18 1 6 CU E7JKE 3 ...
Page 139: ...139 ...
Page 140: ...140 ...
Page 141: ...141 ...
Page 142: ...142 18 1 7 CU E9JKE 3 ...
Page 143: ...143 ...
Page 144: ...144 ...
Page 145: ...145 ...
Page 146: ...146 18 1 8 CU E12JKE 3 ...
Page 147: ...147 ...
Page 148: ...148 ...
Page 149: ...149 ...