16.4.24. F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
• During cooling, compressor frequency = Fcmax.
• During heating, compressor frequency > Fhrated.
• During cooling and heating operation, running current: 0.65A < I < 1.65A.
• During cooling, indoor intake - indoor pipe < 4
°
C
• During heating, indoor pipe - indoor intake < 5
°
C
Multi Models Only
- Gas shortage detection 1: A gas shortage is detected by checking the CT-detected input current value and the compressor
running frequency. During startup and operating of cooling and heating, input current < 8.78/256 (A/Hz) x compressor
running fre 0.25.
- Gas shortage detection 2: A gas shortage is detected by checking the difference between indoor pipe temperature and
indoor intake air temperature during cooling and heating.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage)
• Poor compression performance of compressor.
• 2/3 way valve closed.
• Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
Summary of Contents for CS-E7JKEW
Page 21: ...21 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 27: ...27 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 30: ...30 6 Refrigeration Cycle Diagram 6 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 31: ...31 6 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 32: ...32 6 3 CU E15JKE ...
Page 33: ...33 7 Block Diagram 7 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 34: ...34 7 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 35: ...35 7 3 CU E15JKE ...
Page 36: ...36 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 38: ...38 8 2 2 CU E15JKE ...
Page 39: ...39 8 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 40: ...40 8 2 4 CU E15JKE 1 ...
Page 41: ...41 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 43: ...43 9 2 2 CU E15JKE ...
Page 44: ...44 9 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 45: ...45 9 2 4 CU E15JKE 1 ...
Page 46: ...46 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 47: ...47 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 49: ...49 10 2 Outdoor Unit 10 2 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 50: ...50 10 2 2 CU E15JKE ...
Page 51: ...51 10 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 113: ...113 17 1 3 To remove discharge grille ...
Page 114: ...114 17 1 4 To remove control board 17 1 5 To remove cross flow fan and indoor fan motor ...
Page 115: ...115 ...
Page 118: ...118 18 Technical Data 18 1 Operation Characteristics 18 1 1 CU E7JKE ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...121 ...
Page 122: ...122 18 1 2 CU E9JKE ...
Page 123: ...123 ...
Page 124: ...124 ...
Page 125: ...125 ...
Page 126: ...126 18 1 3 CU E12JKE ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 18 1 4 CU E15JKE ...
Page 131: ...131 ...
Page 132: ...132 ...
Page 133: ...133 ...
Page 134: ...134 18 1 5 CU E15JKE 1 ...
Page 135: ...135 ...
Page 136: ...136 ...
Page 137: ...137 ...
Page 138: ...138 18 1 6 CU E7JKE 3 ...
Page 139: ...139 ...
Page 140: ...140 ...
Page 141: ...141 ...
Page 142: ...142 18 1 7 CU E9JKE 3 ...
Page 143: ...143 ...
Page 144: ...144 ...
Page 145: ...145 ...
Page 146: ...146 18 1 8 CU E12JKE 3 ...
Page 147: ...147 ...
Page 148: ...148 ...
Page 149: ...149 ...