Troubleshooting Methods
• Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
ii. Abnormal Discharge
Judgement Method
• During e-ion operation, when feedback voltage is -Lo (at microcontroller) is detected, it is judged abnormal discharge and
stops power supplies to the e-ion Air Purifying system.
• The unit retries after 30 minutes and repeat for 24 times. (not applicable for e-ion Check Mode)
Troubleshooting Method
• Press “e-ion” button or “OFF/ON” button to stop the operation and check the e-ion Air Purifying system main connector to
PCB.
• After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
• The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
Error Reset Method
• Press “OFF/ON” button to OFF the operation.
• Press AUTO OFF/ON button at indoor unit to OFF the operation.
• OFF Timer activates.
• Press “e-ion” button during e-ion individual mode.
• Power supply reset.
iii. e-ion breakdown
Judgement Method
• When hi-feedback voltage (at microcontroller) supplied to filter during e-ion stop, due to PCB or filter’s high voltage power
supply damage.
• Operations except e-ion continue. Both Timer indicator and e-ion indicator blink.
Troubleshooting Method
• Press “e-ion” button or “OFF/ON” button to stop the operation.
• Change main circuit board or filter’s high voltage power supply.
• When lo-feedback voltage supplied to e-ion Air Purifying system during e-ion operation, e-ion indicator and Timer indicator
stop blinking.
12.13. Mild Dry Cooling Operation
• This operation helps to prevent decreases in room humidity while maintaining the setting temperature.
• During unit running at Cooling operation mode, if “Mild Dry Cooling” button is pressed, Mild Dry Cooling operation starts and Mild
Dry Cooling indicators turns ON.
• Mild dry cooling operation is unavailable when the unit is operating Auto mode, Soft Dry mode, Patrol individual operation or
e-ion individual operation.
• Mild dry cooling operation is cancelled when the unit turned OFF, or when the operation mode changed from Cooling to other
mode.
• Powerful, Quiet and Mild Dry Cooling mode cannot function at the same time, the unit will follows the operation according to the
last signal received.
• During this operation, the compressor frequency changes according to operating condition to prevent room humidity decreases
and when AUTO AIR SWING is set, the vertical airflow direction fixed at lower limit position.
Summary of Contents for CS-E7JKEW
Page 21: ...21 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 27: ...27 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 30: ...30 6 Refrigeration Cycle Diagram 6 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 31: ...31 6 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 32: ...32 6 3 CU E15JKE ...
Page 33: ...33 7 Block Diagram 7 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 34: ...34 7 2 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 35: ...35 7 3 CU E15JKE ...
Page 36: ...36 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 38: ...38 8 2 2 CU E15JKE ...
Page 39: ...39 8 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 40: ...40 8 2 4 CU E15JKE 1 ...
Page 41: ...41 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 42: ...42 9 2 Outdoor Unit 9 2 1 CU E7JKE CU E9JKE CU E12JKE ...
Page 43: ...43 9 2 2 CU E15JKE ...
Page 44: ...44 9 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 45: ...45 9 2 4 CU E15JKE 1 ...
Page 46: ...46 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 47: ...47 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 49: ...49 10 2 Outdoor Unit 10 2 1 CU E7JKE CU E9JKE CU E12JKE CU E15JKE 1 ...
Page 50: ...50 10 2 2 CU E15JKE ...
Page 51: ...51 10 2 3 CU E7JKE 3 CU E9JKE 3 CU E12JKE 3 ...
Page 113: ...113 17 1 3 To remove discharge grille ...
Page 114: ...114 17 1 4 To remove control board 17 1 5 To remove cross flow fan and indoor fan motor ...
Page 115: ...115 ...
Page 118: ...118 18 Technical Data 18 1 Operation Characteristics 18 1 1 CU E7JKE ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...121 ...
Page 122: ...122 18 1 2 CU E9JKE ...
Page 123: ...123 ...
Page 124: ...124 ...
Page 125: ...125 ...
Page 126: ...126 18 1 3 CU E12JKE ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 18 1 4 CU E15JKE ...
Page 131: ...131 ...
Page 132: ...132 ...
Page 133: ...133 ...
Page 134: ...134 18 1 5 CU E15JKE 1 ...
Page 135: ...135 ...
Page 136: ...136 ...
Page 137: ...137 ...
Page 138: ...138 18 1 6 CU E7JKE 3 ...
Page 139: ...139 ...
Page 140: ...140 ...
Page 141: ...141 ...
Page 142: ...142 18 1 7 CU E9JKE 3 ...
Page 143: ...143 ...
Page 144: ...144 ...
Page 145: ...145 ...
Page 146: ...146 18 1 8 CU E12JKE 3 ...
Page 147: ...147 ...
Page 148: ...148 ...
Page 149: ...149 ...