8.2. Protection Control Features
8.2.1. Protection Control For All Operations
8.2.1.1. Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
8.2.1.2. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
8.2.1.3. Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 2 minutes.
E24DK
Operation Mode
X (A)
Y (A)
Cooling/Soft Dry (A)
12.8
20.0
Cooling/Soft Dry (B)
10.3
20.0
Heating
13.0
20.0
4. The first 30 minutes of cooling operation, (A) will be applied.
31
CS-E24DKE CU-E24DKE
Summary of Contents for CS-E24DKE
Page 9: ...4 Dimensions 4 1 Indoor Unit Remote Control 9 CS E24DKE CU E24DKE ...
Page 10: ...4 2 Outdoor Unit 10 CS E24DKE CU E24DKE ...
Page 11: ...5 Refrigeration Cycle Diagram 11 CS E24DKE CU E24DKE ...
Page 12: ...6 Block Diagram 12 CS E24DKE CU E24DKE ...
Page 13: ...7 Wiring Diagram 13 CS E24DKE CU E24DKE ...
Page 77: ...13 Technical Data 77 CS E24DKE CU E24DKE ...
Page 89: ...89 CS E24DKE CU E24DKE ...
Page 91: ...18 3 Remote Control 91 CS E24DKE CU E24DKE ...
Page 92: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 92 CS E24DKE CU E24DKE ...
Page 94: ......