44
13.3. Protection Control For Heating Operation
13.3.1.
Intake Air Temperature Control
Compressor will operate at maximum frequency if below conditions occur:
1. When the indoor intake air temperature is 30
q
C or above.
13.3.2.
Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14
q
C in order to avoid compressor
overloading.
13.3.3.
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
13.3.4.
Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
13.3.5.
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan
motor stop and operation LED blinks.
Summary of Contents for CS-E18JKEW
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE ...
Page 12: ...12 5 2 2 CU RE24JKE ...
Page 13: ...13 6 Refrigeration Cycle Diagram ...
Page 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE ...
Page 15: ...15 7 2 CS RE24JKE CU RE24JKE ...
Page 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE ...
Page 18: ...18 8 2 2 CU RE24JKE ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE ...
Page 21: ...21 9 2 2 CU RE24JKE ...
Page 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE ...
Page 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE ...
Page 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE ...
Page 76: ...76 16 1 3 To remove power electronic controller ...
Page 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Page 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor ...
Page 79: ...79 ...
Page 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit ...