37
[Heating]
• According to indoor pipe temperature, automatic heating fan speed is determined as follows.
B. Feedback control
• Immediately after the fan motor started, feedback control is performed once every second.
• During fan motor on, if fan motor feedback 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error counter
increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan motor error is detected.
Operation stops and cannot on back.
12.1.7.
Outdoor Fan Motor Operation
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation.
12.2. Airflow Direction
1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger
temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
12.2.1.
Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (
q
)
1
2
3
4
5
Heating
Auto with Heat Exchanger
A
20
B
45
Temperature
C
32
Manual
20
32
45
57
68
Cooling and e-ion
Auto
20 ~ 45
Manual
20
26
32
37
45
Soft Dry
Auto
20 ~ 45
Manual
20
26
32
37
45
Summary of Contents for CS-E18JKEW
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE ...
Page 12: ...12 5 2 2 CU RE24JKE ...
Page 13: ...13 6 Refrigeration Cycle Diagram ...
Page 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE ...
Page 15: ...15 7 2 CS RE24JKE CU RE24JKE ...
Page 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE ...
Page 18: ...18 8 2 2 CU RE24JKE ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE ...
Page 21: ...21 9 2 2 CU RE24JKE ...
Page 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE ...
Page 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE ...
Page 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE ...
Page 76: ...76 16 1 3 To remove power electronic controller ...
Page 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Page 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor ...
Page 79: ...79 ...
Page 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit ...