CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
3. Please make flare after inserting the flare nut onto the
copper pipes.
11.3.4. EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
•
Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
•
Be sure to check for gas leakage.
CAUTION
•
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
•
If the leak stops when the piping connections are tightened further, continue working from step 3.
•
If the leak does not stop when the connections are retightened, repair the location of leak.
•
Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
70
Summary of Contents for CS-E18CKE
Page 10: ...4 Dimensions 10 ...
Page 11: ...11 ...
Page 12: ...5 Refrigeration Cycle Diagram 12 ...
Page 13: ...6 Block Diagram 13 ...
Page 14: ...7 Wiring Diagram 14 ...
Page 20: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Dry 2 Heating 20 ...
Page 44: ...9 Operating Instructions 45 46 45 46 46 46 46 46 48 49 47 Ionizer DO NOTTOUCH 44 ...
Page 45: ...49 50 48 47 45 ...
Page 47: ...every 6 months see page 44 see page 48 Soaps Neutral household detergents pH7 47 ...
Page 48: ...refer page 47 48 ...
Page 49: ...48 49 ...
Page 51: ...44 46 46 46 47 47 47 48 47 48 45 51 ...
Page 67: ...3 For the embedded piping This can be used for left rear piping left bottom piping also 67 ...
Page 81: ...13 Technical Data 81 ...
Page 82: ...82 ...
Page 96: ...96 ...
Page 98: ...18 1 REMOTE CONTROL 98 ...
Page 99: ...18 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 99 ...
Page 100: ...18 3 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW 100 MAICO Printed in Malaysia ...