17.1.1 Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Heating Mode
Condition of the
air conditioner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Ô
Ô
Ô
Ô
Ô
Ô
Clogged capillary tube or
Strainer
Ô
Ô
Ô
Ò
Ò
Ò
Short circuit in the indoor unit
Ô
Ô
Ô
Ò
Ò
Ò
Heat radiation deficiency
of the outdoor unit
Ò
Ò
Ò
Ô
Ô
Ô
Inefficient compression
Ò
Ô
Ô
Ò
Ô
Ô
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
Summary of Contents for CS-E12PKEW
Page 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 30: ...30 5 1 2 CS E18PK CS E21PK CS E24PK CS E28PK CS XE18PK CS XE21PK ...
Page 31: ...31 5 2 Outdoor Unit 5 2 1 CU E7PKE CU E9PKE 5 2 2 CU E12PKE CU E15PKE ...
Page 32: ...32 5 2 3 CU E18PKE CU E21PKE ...
Page 33: ...33 5 2 4 CU E24PKE CU E28PKE ...
Page 42: ...42 8 1 2 CS E28PKES ...
Page 48: ...48 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 56: ...56 10 1 6 Human Activity Sensor Printed Circuit Board ...
Page 57: ...57 10 2 Outdoor Unit 10 2 1 CU E7PKE ...
Page 58: ...58 10 2 2 CU E9PKE CU E12PKE CU E15PKE ...
Page 59: ...59 10 2 3 CU E18PKE CU E21PKE ...
Page 60: ...60 10 2 4 CU E24PKE CU E28PKE ...
Page 66: ...66 ...
Page 68: ...68 For Gas side piping please refer table and diagram below ...
Page 76: ...76 ...
Page 140: ...140 Figure 3 Figure 4 18 1 1 3 To remove discharge grille Figure 5 ...
Page 142: ...142 Figure 8 Figure 9 ...
Page 143: ...143 Figure 10 ...
Page 145: ...145 18 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure 15 Figure 16 ...
Page 147: ...147 Figure 20 Figure 21 ...
Page 148: ...148 Figure 22 ...