102
15.2
Protection Control For Cooling & Soft Dry Operation
15.2.1 Outdoor Air Temperature Control
•
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
•
This control will begin 1 minute after the compressor starts.
•
Compressor
frequency will adjust base on outdoor air temperature.
15.2.2 Cooling Overload Control
•
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency).
•
The compressor stop if outdoor pipe temperature exceeds 61°C (E7/9/12/15PK), 63°C (E18/21PK), 65°C
(E24/28PK).
•
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise
protection).
15.2.3 Freeze Prevention Control 1
•
When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop
operating.
•
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C.
•
At the same time, indoor fan speed will be higher than during its normal operation.
•
If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normal
operation.
15.2.4 Freeze Prevention Control 2
•
Control start conditions
o
During Cooling operation and soft dry operation
During thermo OFF condition, indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
o
Either one of the conditions above occurs 5 times in 60 minutes.
•
Control
contents
o
Operation
stops
o
Timer LED blinks and “H99” indicated
15.2.5 Dew Prevention Control 1
•
To prevent dew formation at indoor unit discharge area.
•
This control will be activated if:
o
Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
o
When Cooling or Dry mode is operated more than 20 minutes or more.
•
This control stopped if:
o
Compressor
stopped.
o
Remote control setting changed (fan speed / temperature).
o
Outdoor air temperature and indoor intake temperature changed.
•
Fan speed will be adjusted accordingly in this control.
Summary of Contents for CS-E12PKEW
Page 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 30: ...30 5 1 2 CS E18PK CS E21PK CS E24PK CS E28PK CS XE18PK CS XE21PK ...
Page 31: ...31 5 2 Outdoor Unit 5 2 1 CU E7PKE CU E9PKE 5 2 2 CU E12PKE CU E15PKE ...
Page 32: ...32 5 2 3 CU E18PKE CU E21PKE ...
Page 33: ...33 5 2 4 CU E24PKE CU E28PKE ...
Page 42: ...42 8 1 2 CS E28PKES ...
Page 48: ...48 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 56: ...56 10 1 6 Human Activity Sensor Printed Circuit Board ...
Page 57: ...57 10 2 Outdoor Unit 10 2 1 CU E7PKE ...
Page 58: ...58 10 2 2 CU E9PKE CU E12PKE CU E15PKE ...
Page 59: ...59 10 2 3 CU E18PKE CU E21PKE ...
Page 60: ...60 10 2 4 CU E24PKE CU E28PKE ...
Page 66: ...66 ...
Page 68: ...68 For Gas side piping please refer table and diagram below ...
Page 76: ...76 ...
Page 140: ...140 Figure 3 Figure 4 18 1 1 3 To remove discharge grille Figure 5 ...
Page 142: ...142 Figure 8 Figure 9 ...
Page 143: ...143 Figure 10 ...
Page 145: ...145 18 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure 15 Figure 16 ...
Page 147: ...147 Figure 20 Figure 21 ...
Page 148: ...148 Figure 22 ...