13. Operation
Control
13.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
13.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
13.1.2 Cooling
Operation
13.1.2.1 Thermostat
control
•
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C continue for 3 minutes.
•
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
•
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
13.1.3 Soft Dry Operation
13.1.3.1 Thermostat
control
•
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C continue for 3 minutes.
•
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
•
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
13.1.4 Heating
Operation
13.1.4.1 Thermostat
control
•
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C continue for 3 minutes.
•
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature <
Compressor OFF point.
Summary of Contents for CS-E12PKEW
Page 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 30: ...30 5 1 2 CS E18PK CS E21PK CS E24PK CS E28PK CS XE18PK CS XE21PK ...
Page 31: ...31 5 2 Outdoor Unit 5 2 1 CU E7PKE CU E9PKE 5 2 2 CU E12PKE CU E15PKE ...
Page 32: ...32 5 2 3 CU E18PKE CU E21PKE ...
Page 33: ...33 5 2 4 CU E24PKE CU E28PKE ...
Page 42: ...42 8 1 2 CS E28PKES ...
Page 48: ...48 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 56: ...56 10 1 6 Human Activity Sensor Printed Circuit Board ...
Page 57: ...57 10 2 Outdoor Unit 10 2 1 CU E7PKE ...
Page 58: ...58 10 2 2 CU E9PKE CU E12PKE CU E15PKE ...
Page 59: ...59 10 2 3 CU E18PKE CU E21PKE ...
Page 60: ...60 10 2 4 CU E24PKE CU E28PKE ...
Page 66: ...66 ...
Page 68: ...68 For Gas side piping please refer table and diagram below ...
Page 76: ...76 ...
Page 140: ...140 Figure 3 Figure 4 18 1 1 3 To remove discharge grille Figure 5 ...
Page 142: ...142 Figure 8 Figure 9 ...
Page 143: ...143 Figure 10 ...
Page 145: ...145 18 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure 15 Figure 16 ...
Page 147: ...147 Figure 20 Figure 21 ...
Page 148: ...148 Figure 22 ...