24
12.4.2 Horizontal
Airflow
The horizontal airflow direction louvers can be adjusted manually by hand.
12.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)
Purpose
o
To provide quiet cooling operation compare to normal operation.
Control
condition
o
Quiet operation start condition
When “Quiet” button at remote control is pressed.
Quiet LED illuminates.
o
Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
Powerful button is pressed.
Stop by OFF/ON button.
OFF Timer activates.
Quiet button is pressed again.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if ON timer activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control
contents
o
Auto fan speed is change from normal setting to quiet setting of respective fan speed. This is to reduce
sound of Hi, Me, Lo for 3dB.
o
Manual fan speed for quiet operation is -1 step from setting fan speed.
12.6 Quiet Operation (Heating)
Purpose
o
To provide quiet heating operation compare to normal operation.
Control
condition
o
Quiet operation start condition
When “Quiet” button at remote control is pressed.
Quiet LED illuminates.
o
Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
Powerful button is pressed.
Stop by OFF/ON button.
Timer “off” activates.
Quiet button is pressed again.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Summary of Contents for CS-E12NKUAW
Page 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 9: ...9 5 Dimensions 5 1 Indoor Unit ...
Page 10: ...10 6 Refrigeration Cycle Diagram ...
Page 11: ...11 7 Block Diagram ...
Page 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 13: ...13 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 14: ...14 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 15: ...15 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 34: ...34 15 3 Error Code Table ...
Page 64: ...64 16 1 1 2 To remove discharge grille ...
Page 65: ...65 16 1 1 3 To remove control board 16 1 1 4 To remove cross flow fan and indoor fan motor ...
Page 66: ...66 ...