12. Operation
Control
12.1 Basic
Function
Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operation
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
12.1.1
Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
12.1.2 Cooling
Operation
12.1.2.1 Thermostat
control
Compressor is OFF when intake Air Temperature - Internal Setting Temperature < 2.7°F.
Compressor is ON after waiting for 3 minutes, if the Intake Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.3
Soft Dry Operation
12.1.3.1 Thermostat
control
Compressor is OFF when Intake Temperature - Internal Setting Temperature < -3.6°F.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.4 Heating
Operation
12.1.4.1 Thermostat
control
Compressor is OFF when Intake Temperature - Internal Setting Temperature > 3.6°F.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature <
Compressor OFF point
Summary of Contents for CS-E12NKUAW
Page 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 9: ...9 5 Dimensions 5 1 Indoor Unit ...
Page 10: ...10 6 Refrigeration Cycle Diagram ...
Page 11: ...11 7 Block Diagram ...
Page 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 13: ...13 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 14: ...14 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 15: ...15 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 34: ...34 15 3 Error Code Table ...
Page 64: ...64 16 1 1 2 To remove discharge grille ...
Page 65: ...65 16 1 1 3 To remove control board 16 1 1 4 To remove cross flow fan and indoor fan motor ...
Page 66: ...66 ...