34
11.3.4 Connect the cable to the Outdoor Unit
1 Remove the control board cover from the unit
by loosening the screw.
2
Connection cable
between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 × 1.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier
cord. Do not use joint connection cable.
Replace the wire if the existing wire (from
concealed wiring, or otherwise) is too short.
Terminals on the outdoor unit
Colour of wires
Terminals on the indoor unit
1
2
3
1
2
3
3 Secure the cable onto the control board with
the holder (clamper).
4 Attach the control board cover back to the
original position with screw.
5 For wire stripping and connection requirement,
refer to instruction 11.2.4 of indoor unit.
Earth Wire
longer than
others AC
wires for
safety reason
Terminal
Board
Holder
Indoor and outdoor
cable connection
Indoor Unit
•
Earth wire shall be Yellow/Green (Y/G) in colour
and longer than the other AC wires for safety
reason.
11.3.5 Piping
Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
11.3.5.1
Cutting and flaring the piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the piping
end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
1. To cut
damaged
Cracked Uneven
thickness
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper
pipe
Reamer
2. To remove burrs
Point down
Pipe