30
7 Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor
unit according to the diagram below.
Terminals on the outdoor unit
Colour of wires (connection cable)
Terminals on the indoor unit
(Power supply cord)
Terminals on the isolating devices
(Disconnecting means)
1
2
3
1
2
3
L
N
(L)
(N)
8 Secure the power supply cord and connection cable onto the control board with the holder.
9 Close grille door by tighten with screw and close the front panel.
Recommended
length (mm)
Tape
Connection ca ble
Tape
Power supply cord
Recommended
length (mm)
a b c d e f g
55 35 35 50 40 35 60
Terminal
Board
Control
Board
Earth wire
longer than
others
AC wires
for safety
reason
Holder
Holder
Indoor & outdoor
connection cable
Isolating Devices
Outdoor unit
Power supply
cord
Note:
•
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
•
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
•
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.
Wire st ripping
5 mm
or more
Conductor
over inse rted
No loose st rand
when inse rted
Indoor/outdoor
connection
terminal board
10 ±
1 mm
Conductor
fully inse rted
Conductor not
fully inse rted
(gap bet ween wires)
ACCEPT
PROHIBITED
PROHIBITED