
41
11.3.3 Evacuation of the Equipment
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o
Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0
cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o
Be sure to check for gas leakage.
CAUTION
•
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-01 MPa), in the step
e
above take the following measure:
-
If the leak stops when the piping connections are tightened further, continue working from step
e
.
-
If the leak does not stop when the connections are retightened, repair location of leak.
-
Do not release refrigerant during piping work for installation and reinstallation.
-
Take care of the liquid refrigerant, it may cause frostbite.
Summary of Contents for CS-C12KKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9KKV CS C12KKV ...
Page 14: ...14 5 1 2 CS C18KKV CS C24KKV CS C28KKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9KKV 5 2 2 CU C12KKV ...
Page 16: ...16 5 2 3 CU C18KKV CU C24KKV CU C28KKV ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9KKV CU C9KKV CS C12KKV CU C12KKV ...
Page 19: ...19 7 1 2 CS C18KKV CU C18KKV CS C24KKV CU C24KKV ...
Page 20: ...20 7 1 3 CS C28KKV CU C28KKV ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9KKV CU C9KKV ...
Page 27: ...27 9 2 CS C12KKV CU C12KKV ...
Page 28: ...28 9 3 CS C18KKV CU C18KKV ...
Page 29: ...29 9 4 CS C24KKV CU C24KKV ...
Page 30: ...30 9 5 CS C28KKV CU C28KKV ...
Page 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 32: ...32 10 1 2 Power Printed Circuit Board 10 1 2 1 CS C9KKV CS C12KKV ...
Page 33: ...33 10 1 2 2 CS C18KKV CS C24KKV CS C28KKV ...
Page 76: ...76 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Page 78: ...78 Figure 10 Figure 11 ...
Page 80: ...80 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Page 82: ...82 Figure 21 Figure 22 Figure 23 ...
Page 84: ...84 16 3 1 3 To remove power electronic controller Figure 26 Figure 24 Figure 25 Figure 27 ...