36
11.2 Indoor Unit
11.2.1 How to Fix Installation Plate
The mounting wall is strong and solid enough to prevent if from the vibration.
The centre of installation plate should be at more than
c
at right and left of the wall.
The distance from installation plate edge to ceiling should more than
d
.
From installation plate left edge to unit’s left side is
e
.
From installation plate right edge to unit’s right side is
f
.
○
B
: For left side piping, piping connection for liquid should be about
g
from this line.
: For left side piping, piping connection gas should be about
h
from this line.
1 Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2 Drill the piping plate hole with ø70mm hole-core drill.
o
Putting measuring tape at position as shown in the diagram above.
The hole centre is obtained by measuring the distance namely 128 mm for left and right hole
respectively. Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
o
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to step 3)
11.2.2 To Drill a Hole in the Wall and
Install a Sleeve of Piping
1 Insert the piping sleeve to the hole.
2 Fix the busing to the sleeve.
3 Cut the sleeve until it extrudes about 15mm
from the wall.
Caution
When the wall is hollow, please be sure to use the sleeve for tube
ass’y to prevent dangers caused by mice biting the connecting
cable.
4 Finish by sealing the sleeve with putty or
caulking compound at the final stage.
Summary of Contents for CS-C12KKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9KKV CS C12KKV ...
Page 14: ...14 5 1 2 CS C18KKV CS C24KKV CS C28KKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9KKV 5 2 2 CU C12KKV ...
Page 16: ...16 5 2 3 CU C18KKV CU C24KKV CU C28KKV ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9KKV CU C9KKV CS C12KKV CU C12KKV ...
Page 19: ...19 7 1 2 CS C18KKV CU C18KKV CS C24KKV CU C24KKV ...
Page 20: ...20 7 1 3 CS C28KKV CU C28KKV ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9KKV CU C9KKV ...
Page 27: ...27 9 2 CS C12KKV CU C12KKV ...
Page 28: ...28 9 3 CS C18KKV CU C18KKV ...
Page 29: ...29 9 4 CS C24KKV CU C24KKV ...
Page 30: ...30 9 5 CS C28KKV CU C28KKV ...
Page 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 32: ...32 10 1 2 Power Printed Circuit Board 10 1 2 1 CS C9KKV CS C12KKV ...
Page 33: ...33 10 1 2 2 CS C18KKV CS C24KKV CS C28KKV ...
Page 76: ...76 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Page 78: ...78 Figure 10 Figure 11 ...
Page 80: ...80 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Page 82: ...82 Figure 21 Figure 22 Figure 23 ...
Page 84: ...84 16 3 1 3 To remove power electronic controller Figure 26 Figure 24 Figure 25 Figure 27 ...