Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Saved Control
Starting Current Control
Anti-Freezing Control
•
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
•
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
•
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
•
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
•
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
•
When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
s
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
17
CS-C75KE CU-C75KE / CS-C95KE CU-C95KE / CS-C125KE CU-C125KE
Summary of Contents for CS-C125KE
Page 12: ...4 Dimensions 12 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 13: ...13 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 14: ...5 Refrigeration Cycle Diagram 14 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 15: ...6 Block Diagram 15 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 20: ...Soft Dry Operation Time Diagram 20 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 73: ...73 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 84: ...84 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 86: ...22 1 REMOTE CONTROL 86 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 89: ...89 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE MACC Printed in Malaysia ...