![Panasonic CS-C125KE Service Manual Download Page 63](http://html.mh-extra.com/html/panasonic/cs-c125ke/cs-c125ke_service-manual_256622063.webp)
(No refrigerant in the refrigeration cycle)
Procedure:
1. Connect the vacuum pump to the charge set’s centre
hose.
2. Evacuation for approximately one hour.
•
Confirm that the gauge needle has moved toward -0.1
MPa (-76 cmHg) [vacuum of 4 mmHg or less.]
3. Close the valve (Low side) on the charge set, turn off
the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning
off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
•
Vacuum pump oil
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
11.5. Evacuation
63
CS-C75KE CU-C75KE / CS-C95KE CU-C95KE / CS-C125KE CU-C125KE
Summary of Contents for CS-C125KE
Page 12: ...4 Dimensions 12 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 13: ...13 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 14: ...5 Refrigeration Cycle Diagram 14 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 15: ...6 Block Diagram 15 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 20: ...Soft Dry Operation Time Diagram 20 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 73: ...73 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 84: ...84 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 86: ...22 1 REMOTE CONTROL 86 S C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE ...
Page 89: ...89 CS C75KE CU C75KE CS C95KE CU C95KE CS C125KE CU C125KE MACC Printed in Malaysia ...