Setting and Confirming Communication Conditions
5-4
5.2.2 Settings Using FPWIN GR7 (For Serial Communication Unit)
Applications and communication conditions for each communication port should be set using
the tool software FPWIN GR7.
The explanation below shows the case that the serial communication unit is registered in the
slot number 1.
PROCEDURE
1. Select "Options" > "FP7 Configuration" in the menu bar.
The "FP7 Configuration" dialog box appears.
2. Select "I/O map" in the left pane.
The "I/O map" dialog box is displayed.
3. Select the Slot No. in which SCU unit is registered in the "I/O map" dialog box,
and press the "Advanced" button.
The "SCU Unit Settings" dialog box is displayed.
4. Select COM No. in the left pane.
Setting items available for each COM. number are displayed.
5. Set communication conditions, and press [OK] button.
The set conditions are reflected in the project being edited.