D.8 Analog input block
The analog input (
AI
) block (see
figure 31
below) is designed
as a generalized signal conditioning function. The output
from an
AI
block can be connected to the fieldbus. The
AI block receives and processes data measured by the
transducer block
and provides additional functions such
as scaling, filtering, alarm generation, and trending.
D.9 PID block
Figure 31: Analog input (AI) block
The
PID
function offers control based on a programmable
algorithm. The
PID
function block may be used with a valve
to control flow.
Note:
See foundation fieldbus specifications for more detail
on use of the
PID
block.
D.10 Error handling
The flow meter publishes the
error status
on the fieldbus
along with the real data. The error status can be seen in the
CH_x_reported
error
parameter on the
channel transducer
block
. In addition, the
quality
parameter shown with each
of the process variables reports the error. In
figure 32
below,
the
CH1_REPORTED_ERROR
shows as
E1
.
Note:
For more information on the actual measurement
errors and possible causes, see
chapter 3, error codes and
troubleshooting
.
Figure 32: Reported error
Whenever the meter is in measurement error, the
quality bit
for the published parameter shows
bad
quality
(see
figure 33
below). To change the quality bit to
good
, the
measurement error at the meter must be removed.
Notice the
QUALITY.STATUS
field shows as
bad
and the
SUBSTATUS
field shows as
sensor failure
. This information
indicates a measurement error which must be corrected.
Figure 33: Quality bit error
64