Table 6: XMT1000 modbus register map - revision 4.19
Reg #
in hex
Access
level
Register ID
Description
Units
RO/
RW
Size in
bytes
Format
Log real RO
E00
Log int RO
F00
F00
N/A
eLog_NumRecord
Number of
records
Unitless
RO
4
INT32
MAIN Aout real RW
1000
1000
Operator
eAout1_ErrValue
Analog out 1
error handling value
8
RW
4
(IEEE 32 bit)
1002
Operator
eAout1_ZeroValue
Analog out 1 zero
8
RW
4
(IEEE 32 bit)
1004
Operator
eAout1_spanValue
Analog out 1 span
8
RW
4
(IEEE 32 bit)
1006
Operator
eAout1_TestValue
Analog out 1
test value
(percent of span)
12
RW
4
(IEEE 32 bit)
1008
Operator
eAout1_BaseValue
Analog out 1
base value
1, 9, 14, 17, 20 RW
4
(IEEE 32 bit)
100A
Operator
eAout1_FullValue
Analog out 1
full value
1, 9, 14, 17, 20 RW
4
(IEEE 32 bit)
HART Aout real RW
1010
1010
Operator
eAout2_ErrValue
Analog out 2
error handling value
8
RW
4
(IEEE 32 bit)
1012
Operator
eAout2_ZeroValue
Analog out 2
zero
8
RW
4
(IEEE 32 bit)
1014
Operator
eAout2_spanValue
Analog out 2
span
8
RW
4
(IEEE 32 bit)
1016
Operator
eAout2_TestValue
Analog out 2
test value
(percent of span)
12
RW
4
(IEEE 32 bit)
1018
Operator
eAout2_BaseValue
Analog out 2
base value
1, 9, 14, 17, 20 RW
4
(IEEE 32 bit)
101A
Operator
eAout2_FullValue
Analog out 2
full value
1, 9, 14, 17, 20 RW
4
(IEEE 32 bit)
33
Summary of Contents for PanaFlow XMT1000
Page 1: ...PanaFlow XMT1000 User s manual 910 313 Rev A...
Page 2: ...ii...
Page 4: ...no content intended for this page iv...
Page 79: ...71...