Control Panel: OPERATION AND FUNCTIONS
ON/OFF
Exit from Menu
K1
A
1
2
K3
Scroll/Increase
Service Grill
Manual Start Damper
User Menu Entry
Probes Menu
K2
K4
Scroll/Decrease
Fig. 3 Main Screen
Temperature Probe S1
On:
Fan On
Flashing:
Fan in Safety mode
2
Probe S2 Displayed
MANUAL Mode
Spark Function Active
AUTOMATIC Mode
SERV Output Active
PROPORTIONAL Mode
5.
FUNCTIONS
5.1
ON/OFF
ON/OFF of the control unit is done by prolonged pressure on the
K1
button
The OFF status is indicated by the lit
K1
button
The following sequence of messages is displayed when the control unit is turned on
o
Product Code
F002
o
Product Revision
r 0.4
5.2
MODES OF OPERATION
[P17 = 1; INPUT S1 = Probe NTC100K]
It is possible to choose from among three Modes of Operation:
MANUAL
: indication light
The fan operates at the speed set by the user in an independent way from the
S1 Probe
.
AUTOMATIC:
indication light
The fan operates at the speed set by the user, if the temperature of the
S1 Probe
is greater than
E01
.
PROPORTIONAL:
indication light
The fan operates at the speed selected by the temperature control unit, depending on the temperature of the
S1 Probe
.
The temperature range where the transmission power is active goes from
E01
to
E01+E50
[P17 = 2; INPUT S1 = Thermostat]
AUTOMATIC:
indication light
;
displays the word
AUTO
The fan operates at the speed set by the user, if the temperature of the
S1 Probe
is greater than
E01
.
5.3
SAFETY FUNCTION [P17 = 1]
This function is active if
P04
=
1
and allows to dissipate the excess heat in the stove.
If the temperature detected by the
S1 Probe
exceeds the value of the Safety Thermostat
E02
and the Fan is switched
off in MANUAL Mode or by the Room Temperature Thermostat, the operation moves to PROPORTIONAL Mode
with a delay of 10 seconds.
5.4
ALARM FUNCTION [P17 = 1]
If the temperature detected by the
S1 Probe
exceeds the value of the Alarm Thermostat
E03
If the
P05 = 1
parameter is activated, an acoustic and visual warning is triggered (the temperature flashes on the Display)
SILENCE
Function: the acoustic signal can be turned off for 5 minutes by pressing on any button. If the alarm
condition persists, the acoustic signal is reactivated.
The Operation moves to PROPORTIONAL Mode with a delay of 10 seconds.
5.5
FAN SAFETY FUNCTION [P17 = 1]
This function is active if
P03
=
1
. If the temperature detected by the
S1 Probe
exceeds the value of the Fan Safety
Thermostat
E04
, the Fan is switched off to avoid damaging it.
5.6
STANDBY FUNCTION [P17 = 1]
In the case of the device
TURNED OFF
, if the temperature of the
S1 Probe
exceeds the value of the
E02
or
E03
thermostat
The device automatically moves to the
ON
state