AFR
- WATERFAN HEATER
Manual
FURTHER INFORMATION: HTTP://WWW.PAKOLE.HU
22
Intelligent automatic controll
Menu
No
Description
Meaning/explanation
Regulation
01
The mount of degrees Celsius which changes fan speed. The
standard threshold level is set 1°C which means that the thermostat
activates heating if the outside temperature is less than 0,5°C than
the required/set temperature and switches heating off if the outside
temperature is more than 0,5°C than the required/set temperature.
When the minimum threshold level is 2°C, thermostat activates
heating if the outside temperature is less than 1°C than the required/
set temperature and switches heating off if the outside temperature is
more than 1°C than the required/set temperature.
Factory
settings: 1°C,
Regulation
ranges from
1°C to 10°C
02
Menu allows you to calibrate displayed room temperature
- 1°C = tempe-
raturę reduction
by 1°C
0°C = tempera-
turę unchanged
1°C = increase
by 1°C
03
Menu allows you to select °C or °F
°C = °C
°F = °F
04
Menu allows you to select 12-hour or 24-hour clock
Factory
settings: 24H,
options: 24H
lub 12H
05
Operation options – fan may run continuously or only when heating/
cooling system is on
1 = fan working
when heating
system is
on (factory
settings)
0 = fan runs
continuously
Sensitivity adjustment
of controller
Menu No.
Menu No.
Temperature
calibration
Temperature
fomat
Menu No.
Menu No.
Clock fomrat
Fan operation
modes
Menu No.
Error warning
If any errors have occurred, one of the following messages will be displayed:
LO
– room temperature is below 0°C,
HI
– room temperature is higher than 50°C,
ERR
–electrical shorts or controller is damaged