SECTION 5
REMOTE OPERATION
81
5.3.1 STEADY-STATE OUTPUT PARAMETERS
FORM,<n>
sets Output Power Form of selected program.
n
= <1>Single
Φ
, <2>Split
Φ
, or <3>Three
Φ
COUPLing,<s>
sets Output coupling of selected program.
s
= <DIRECT> or <XFMR>
XFMRRATIO,<n.nn>
sets Output XFMR ratio (n.nn:1) of selected program.
n.nn
= <0.05> to <5.00>
FREQuency,<n>
sets Output Frequency of selected program.
n
= <:SOUR:FREQ:LIM:MIN> to <:SOUR:FREQ:LIM:MAX> Hz.
VOLTage,<n>
sets Output VOLTAGE
Φ
A,
Φ
B,
Φ
C of selected program.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
VOLTage1,<n>
sets Output VOLTAGE
Φ
A of selected program.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
VOLTage2,<n>
sets Output VOLTAGE
Φ
B of selected program.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
VOLTage3,<n>
sets Output VOLTAGE
Φ
C of selected program.
n
= <0> to <150, or 150 x XFMRRATIO> Volts
CURRent:LIMit, <n>
sets Output Current Limit of selected program.
n
= <0> to <AMPS meter range> Amps
PHASe2,<n>
sets Output
Φ
angle B of selected program.
n
= <0> to <359> degrees
PHASe3,<n>
sets Output
Φ
angle C of selected program.
n
= <0> to <359> degrees
WAVEFORM,<n>
sets Output Waveform
Φ
A,
Φ
B,
Φ
C of selected program.
n
= <1> to <16>
WAVEFORM1,<n>
sets Output Waveform
Φ
A of selected program.
n
= <1> to <16>
WAVEFORM2,<n>
sets Output Waveform
Φ
B of selected program.
n
= <1> to <16>
WAVEFORM3,<n>
sets Output Waveform
Φ
C of selected program.
n
= <1> to <16>
EVENTS <n>
sets number of times to repeat the transient portion of the selected program
when the Transient is executed.
n
= 0-65535. A value of 0 specifies continuous repetition.
Summary of Contents for UPC-3
Page 2: ......
Page 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Page 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 3 Figure 1 3b UPC 3 Figure 1 3c UPC 1 ...
Page 43: ...SECTION 4 OPERATION 31 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Page 74: ...SECTION 4 OPERATION 62 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...