LMX SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 255 of 463
Query Format
[SOURce:]FREQuency:LIMit:RANGe?
Description
This command returns the lower and upper frequency user limit set
value.s
Returned Data Format
<nr2>, <nr2>
Query Example
FREQ:LIM:RANG?
53.0000,63.0000
Command Syntax
[SOURce:]FREQuency:SLEW
Description
Sets the frequency slew rate in Hz/msec.
Parameters
0.01 – 5000.00
Parameter Format
<nr2>
Example
FREQ:SLEW 100.0
Query Format
[SOURce:]FREQuency:SLEW?
Returned Data Format
<nr2>
Query Example
FREQ:SLEW?
100.0000
Query Format
[SOURce:]FREQuency:SPAN?
Description
This command is provided to support backward compatibility with
Pacific Power UPC controllers. Refer also to the
“
SYSTem:COMPatible”
command. For LMX Series®, this query
always returns 5000.0000
Returned Data Format
<nr2>
Query Example
FREQ:SPAN?
5000.0000
8.7.4
Current Programming Commands
Command Syntax
[SOURce:]CURRent:LIMit#
Description
This command sets the programmable current level for the selected
phase #. If # is omitted, sets all phases to current level specified. The
value set cannot exceed the maximum current capability of the
power source as returned by the “
[SOURce:]CURRent:LIMit#:MAX?”
command.
If the load current exceeds the current limit set point, the source will
go into constant current mode to maintain the load current at the set
limit level.
Parameters
0.00 – MAX
Parameter Format
<nr2>
Example
CURR:LIM 20.5
Query Format
[SOURce:]CURRent:LIMit#?
Returned Data Format
<nr2>
Query Example
CURR:LIM?
41.667,41.667,41.667