Mobile Home Installation
Warning:
Under no circumstances is this heater to be installed in a makeshift or "temporary" manner. It may
be fired only after the following conditions have been met.
• DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
• DO NOT INSTALL IN A SLEEPING ROOM.
• CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/
ROOF MUST BE MAINTAINED.
• Attach the stove to the floor using two 1/4" x 2" or longer lag screws through holes in the legs or the
Pedestal base.
• Outside combustion air supply must be used for Mobile Home installations - See "Combustion Air" on
page 17.
• The services of a competent or certified installer, are strongly recommended:
NFI (National Fireplace Institute®) in the United States,
CSIA (Chimney Safety Institute of America) in the United States and Canada,
WETT (Wood Energy Technology Transfer) in Canada or
APC (Association des Professionnels du Chauffage) in Quebec
Clearances
This heater must be installed with listed double-wall connector and compatible ULC-S629 or UL-103HT listed
chimney system.
Clearances to combustible surfaces and materials are shown. See picture below.
Consult local fire codes and authorities for approval.
NOTE:
Install all components to the connector or chimney manufacturer's installation requirements. Consult
your chimney supplier/manufacturer for installation advice.
15 5/8"
397mm
22 1/2"
572mm
8"
203mm
11"
279mm
5"
127mm
3"
76mm
3"
76mm
Mobile Home
Minimum
Clearances to
Combustibles
Double Wall Connector
Figure 13: NEO2.5 mobile home clearances.
Neo 2.5LE_141119-32
22
100003380
Neo 2.5 LE_14119-32