Residential Installation
Clearances:
Clearances may be reduced with various heat shielding/insulating materials. Consult CSA B365 or NFPA 211
and local fire codes and authorities for approval. For close clearances, use a listed double-wall connector.
NOTE: local/national codes or regulations may override some guidelines in this manual
We recommend that our products be installed and/or serviced by professionals who are certified by a
“Qualified agency”;
NFI (National Fireplace Institute®) in the United States,
CSIA (Chimney Safety Institute of America) in the United States and Canada,
WETT (Wood Energy Technology Transfer) in Canada or
APC (Association des Professionnels du Chauffage) in Quebec
18"
457mm
12"
305mm
26 1/2”
673mm
20 5/8"
524mm
8"
203mm
11"
279mm
5"
127mm
15 5/8"
397mm
3"
76mm
8"
203mm
3"
76mm
8"
203mm
8"
203mm
22 1/2"
572mm
8"
203mm
11"
279mm
5"
127mm
22 1/2"
572mm
ALCOVE:
Min. Height 7’ [2.134m]
Max. Depth 36” [915mm]
Single Wall Connector - Residential
Double Wall Connector - Residential
Residential
Minimum
Clearance to
Combustibles
Figure 6: NEO 2.5 LE Residential clearances.
18"
457mm
12"
305mm
26 1/2”
673mm
20 5/8"
524mm
8"
203mm
11"
279mm
5"
127mm
15 5/8"
397mm
3"
76mm
8"
203mm
3"
76mm
8"
203mm
8"
203mm
22 1/2"
572mm
8"
203mm
11"
279mm
5"
127mm
22 1/2"
572mm
Conduit à paroi simple
Alcove: Min. la taille 2.13m (7 pi)
Max. profondeur 915 m m (3 pi)
Neo 2.5 LE_14119-32