Floor Protector
The stove may be installed on a combustible floor provided noncombustible ember protection is used.
This protection must extend as follows:
In USA: 16" (406 mm) to the front and 8" (203 mm) to the sides of the fuel loading door opening. See Figure
4, below.
In Canada: 18" (457 mm) on the firing side and 8" (203 mm) to the other sides (Figure 5).
This protection is also required under the chimney connector and 2" (51 mm) beyond each side.
Canada Only
Minimum Width - 45"(1.14m)
Minimum Overall Depth - 49 3/8"(1.25m)
8” [203mm]
8” [203mm]
8” [203mm]
18” [457mm]
Non - combustible floor protector
16" [406mm]
U.S.A. Only
Minimum Width - 35"(889mm)
Minimum Overall Depth - 37 3/8"(950mm)
(Type 1 floor protector - approved to UL1618)
Minimum 20GA steel
Non - combustible floor protector
8” [203mm]
8” [203mm]
Figure 4: NEO 2.5LE Floor Protector USA Only.
Figure 5: NEO 2.5LE Floor protector Canada only.