Floorplan
2.2
The EVSE is designed for a side-by-side installation, with the back of the cabinet against a wall or
freestanding. Due to air cooled ventilation the bottom of the EVSE has to be free from debris or
obstruction.
It is mandatory to respect a clearance of 100 mm at the rear and in between separate units. In the
front, the recommended clearance is 1500 mm to provide space for servicing the equipment. Note
that these clearances may be significantly impacted by site-specific situations such as a restriction
in accessibility that require further clearance consideration for egress. Please consult with local site
engineering as needed.
Measurements shown in the image below are recommended clearances. 10 mm is the minimum
clearance between the EVSE and other EVSE or objects at the back and sides. This clearance
requires a fork-lift installation.
* 100 mm of clearance between units at the back and sides is the recommended in order to allow
space provisions that make the installation possible with a crane or hoist.
Note: The two cabinets are linked with each other.
Maintenance area
Caution
When planning a site layout, additional space may be required to allow for a safe
route of egress. All local codes for safe egress must be followed.
7