VZR.247800.001
IM
Turnstile CUBE C-03
Installation Manual
21
5.3 Connecting the access control system (optional)
The ACS controller should be connected to the group of the following
contacts:
ACCES_IN and ACCES_OUT
.
Identification of contacts: LEFT, RIGHT, STOP, АР, GND. The contact
assignment is shown in Table 2.
Table 2
– Assignment of the ACS contacts
Identification of contacts
Assignment of contacts
LEFT, RIGHT
one-time passing left/ right
(lower priority)
STOP
passing forbidden ("Stop" mode)
(medium priority)
GND
common contact
AP
free passage in both directions ("Antipanic")
(highest priority)
Inputs for connecting the ACS differ by priority:
1)
AP input has the highest priority. If the AP command was sent to this input (the AP
made contact with the GND contact), the turnstile is in free passage mode and
DOES NOT
RESPOND(!)
to any commands other than STOP; the green arrows are flashing in both
directions on the indication panel. The AP command can be withdrawn either by the STOP
command from the ACS (or panel), or by rebooting the turnstile.
2)
LEFT and RIGHT have the same low priority and include a one-time one side passing. If
both inputs are closed, passing is allowed in the side whose input closed first. If pass is not
completed, the turnstile will automatically switch to STOP mode after 5 seconds.
3)
Free access in both directions can be enabled only in potential control mode by
simultaneous feeding of signals to the LEFT and RIGHT inputs or by sequential feeding of
the LEFT and RIGHT signals.