6. SETTING UP THE DEVICE
6.1. Setting up the device is fluid level monitoring channels sensitivity adjustment. To set up the
device follow given directions.
6.2. Switch on power 220 VAC 50 Hz and make sure that LED POWER on the front panel of the
device lights up.
6.3. Fill the reservoir up gradually and check lighting up LEDs LEVEL 3, LEVEL 2 and LEVEL 1 on
the front panel of the device as soon as the fluid reaches appropriated electrodes.
If one or more LEDs didn’t light up while the reservoir is filling you should increase level
monitoring channel’s sensitivity.
To change channel sensitivity use commutators X2 (channel “Level 1”), X3 (channel “Level 2”)
or X4 (channel “Level 3”). Level’s sensitivity increases when sequence number of commutator’s
jumper’s position increases and it decreases when sequence number of commutator’s jumper’s
position decreases.
CAUTION!
The device’s connector block is under tension 220 VAC 50 Hz which is dangerous
for human life. Changing commutator’s jumpers position is possible only when the device is completely
currentless.
6.4. Make gradually emptying of the reservoir and check going out LEDs LEVEL 1, LEVEL 2 and
LEVEL 3 on the front panel of the device.
If one or more LEDs don’t go out while the reservoir is emptying you should decrease level
monitoring channel’s sensitivity according p. 6.3.
6.5. To check up sensitivity settings quality make reservoir full and empty again and check if
level sensors work well by LEDs LEVEL 1, LEVEL 2 and LEVEL 3.
After doing this work the device is ready to operation.