S-93--E
■
Example of high alarm setup
Given below is an example of setting up the alarm for high alarm.
●
Setup example (where "alarm hysteresis" and "alarm immunity time" are involved.)
・
Alarm conditions:
When the following condition continues beyond the alarm immunity time.
Instant flowrate
≧
Alarm setpoint
・
Alarm cancel conditions: Instant flowrate < Alarm setpoint - Alarm hysteresis
Stays off
Alarm 2 setpoint
Flowrate
→
[L
/min(normal)]
Alarm 2 hysteresis
Instant flowrate
OFF
Comes on
ON
Stays off
OFF
Comes on
ON
Alarm 2 LED
Alarm 2 output
Time
→
Within alarm immunity time →
Beyond alarm immunity time →
NOTES: If alarm status (lower digit) is set to "o", the "ON" and "OFF" of alarm output become the
opposite states shown in the above figure.
●
Setup example (where "alarm hysteresis" exists and "alarm immunity time" is set to "0".)
・
Alarm conditions :
Instant flowrate
≧
Alarm setpoint
・
Alarm cancel conditions : Instant flowrate < Alarm setpoint - Alarm hysteresis
Stays off
Alarm 2 setpoint
Flowrate
→
[L
/min(normal)]
Instant flowrate
OFF
Comes on
ON
Stays off
OFF
Comes on
ON
Alarm 2 LED
Alarm 2 output
Time
→
Alarm 2 hysteresis
NOTES: When alarm status (lower digit) is set to "o", the "ON" and "OFF" of alarm output become
the opposite states shown in the above figure.
Parameter Name
Setting
Alarm setpoint
[L/min (normal)]
0
Alarm hysteresis
[L/min (normal)]
0
Alarm status
(higher digit)
H
Alarm status
(lower digit)
S
Alarm immunity
time
[sec]
3
Parameter Name
Setting
Alarm setpoint
[L/min (normal)]
0
Alarm hysteresis
[L/min (normal)]
0
Alarm status
(higher digit)
H
Alarm status
(lower digit)
S
Alarm immunity
time
[sec]
0