17.2 Setting Communication Functions
Setting of communication functions is carried out in the CHECK submenu under the Setup menu.
■
Setting baud rate
Baud rate is set from "bAud.r" of the CHECK submenu under the Setup menu. It can be selected from
9600bps, 19200bps, or 38400bps.
→
Refer to "12.5 Display Transition (5) Setting Diagnosis and Maintenance Functions".
■
Setting polling address
Polling address is set from "P.Addr" of the CHECK submenu.
→
Refer to "12.5 Display Transition (5) Setting Diagnosis and Maintenance Functions".
Polling address is set for identifying the instrument when two or more instruments are connected at the
multiple points on the same communication line. Be sure to set the polling address so that no instruments of
the same address exists on the same communication line. In the case of 1 to 1 connection, use the default
value (0).