Specifications
900-0198-01-00 Rev A
57
Table 26
48-Volt Inverter Settings (MATE3)
Field
Item Default
Minimum
Maximum
INVERTER
Hot Key
Inverter Mode
Off On
,
Off
, or
Search
CHARGER
Hot Key
Charger Control
On On
or
Off
AC Input
Hot Key
AC Input Mode
Use Drop
or
Use
Search
Sensitivity
(see page 14 for increments)
6
0
50
Pulse Length
8 AC Cycles
4 AC Cycles
20 AC Cycles
Pulse Spacing
60 AC Cycles
4 AC Cycles
120 AC Cycles
AC Input and
Current Limit
Input Type
Grid
Grid
or
Gen
Grid Input AC Limit
28 Aac
5 Aac
30 Aac
Gen Input AC Limit
28 Aac
2 Aac
30 Aac
Charger AC Limit
FX3048MT 12Aac
0
Aac
14
Aac
VFX3648M
18 Aac
0 Aac
20 Aac
Grid AC Input
Voltage Limits
Voltage Limit Lower
108 Vac
40 Vac
115 Vac
(Voltage Limit)
Upper
140 Vac
130 Vac
150 Vac
Transfer Delay
0.1 second
0.12 seconds
4.0 seconds
Gen AC Input
Voltage Limits
Voltage Limit Lower
108 Vac
40 Vac
115 Vac
(Voltage Limit)
Upper
140 Vac
130 Vac
150 Vac
Transfer Delay
1.0 second
0.12 seconds
4.0 seconds
Connect Delay
0.5 minutes
0.2 minutes
15.0 minutes
AC Output
Output Voltage
120 Vac
110 Vac
125 Vac
Low Battery
Cut-Out Voltage
42 Vdc
36 Vdc
48 Vdc
Cut-In Voltage
50 Vdc
44 Vdc
52 Vdc
Battery Charger
Absorb Voltage
57.6 Vdc
52 Vdc
64 Vdc
(Absorb)
Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
54.4 Vdc
48 Vdc
60 Vdc
(Float)
Time
1.0 hours
0.0 hours
24.0 hours
Re-Float Voltage
50 Vdc
44 Vdc
52 Vdc
Battery Equalize
Equalize Voltage
57.6 Vdc
56 Vdc
34 Vdc
(Equalize)
Time
1.0 hours
0.0 hours
24.0 hours
Auxiliary Output
Aux Control
Auto
Off, Auto
or
On
Aux Mode
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed
, or
Remote
(Load Shed)
Enable Voltage
44 Vdc
40 Vdc
56 Vdc
(Gen Alert)
ON Voltage
44 Vdc
40 Vdc
56 Vdc
(Gen Alert ON)
Delay
4 minutes
0 minutes
240 minutes
(Gen Alert)
OFF Voltage
56 Vdc
48 Vdc
72 Vdc
(Gen Alert OFF)
Delay
9 minutes
0 minutes
240 minutes
(Vent Fan)
Enable Voltage
52 Vdc
40 Vdc
64 Vdc
(Vent Fan)
Off Period
5 minutes
0 minutes
30 minutes
(Divert DC or AC)
Enable Voltage
58.4 Vdc
48 Vdc
64 Vdc
(Divert DC or AC)
Off Delay
30 seconds
0 seconds
240 seconds
Inverter Stacking
Stack Mode
Master
1-2phase Master, Classic Slave, OB Slave L1,
OB Slave L2, 3phase Master, 3phase Slave
Power Save
Ranking
Master Adjust Only
0 0
7
Slave Adjust Only
1 1
15
Grid-Tie Sell
Grid Tie Enable
— Inoperative
Sell Voltage
— Inoperative
Grid Tie Window
— Inoperative
Calibrate
Input Voltage
27
-1 -3
1
Output Voltage
27
-1 -3
1
Battery Voltage
28
0.0 -0.8
0.8
27
These values represent an adjustable setting with a total range of 4 Vac. The default value of -1 means the calibration will subtract 1 volt from the measured value.
The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it. The result is also displayed.
28
These values represent an adjustable setting with a range of ± 0.8 Vdc from the measured value. The range of settings allows up to 0.8 volts to be either added or
subtracted from the measured value (in increments of 0.4 Vdc). The result is also displayed.