Table 25
36-Volt Inverter Settings (MATE3)
Field
Item Default
Minimum
Maximum
INVERTER
Hot Key
Inverter Mode
Off On
,
Off
, or
Search
CHARGER
Hot Key
Charger Control
On
On
or
Off
AC Input
Hot Key
AC Input Mode
Use Drop
or
Use
Search
Sensitivity
(see page 14 for increments)
6
0
50
Pulse Length
8 AC Cycles
4 AC Cycles
20 AC Cycles
Pulse Spacing
60 AC Cycles
4 AC Cycles
120 AC Cycles
AC Input and
Current Limit
Input Type
Grid
Grid
or
Gen
Grid Input AC Limit
28 Aac
5 Aac
30 Aac
Gen Input AC Limit
28 Aac
2 Aac
30 Aac
Charger AC Limit
FX2536MT
12 Aac
0 Aac
14 Aac
VFX3236M
18 Aac
0 Aac
20 Aac
Grid AC Input
Voltage Limits
Voltage Limit Lower
108 Vac
40 Vac
115 Vac
(Voltage Limit)
Upper
140 Vac
130 Vac
150 Vac
Transfer Delay
0.1 second
0.12 seconds
4.0 seconds
Gen AC Input
Voltage Limits
Voltage Limit Lower
108 Vac
40 Vac
115 Vac
(Voltage Limit)
Upper
140 Vac
130 Vac
150 Vac
Transfer Delay
1.0 second
0.12 seconds
4.0 seconds
Connect Delay
0.5 minutes
0.2 minutes
15.0 minutes
AC Output
Output Voltage
120 Vac
110 Vac
125 Vac
Low Battery
Cut-Out Voltage
31.5 Vdc
27 Vdc
36 Vdc
Cut-In Voltage
37.5 Vdc
33 Vdc
39 Vdc
Battery Charger
Absorb Voltage
43.2 Vdc
39 Vdc
48 Vdc
(Absorb)
Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
40.8 Vdc
36 Vdc
45 Vdc
(Float)
Time
1.0 hours
0.0 hours
24.0 hours
Re-Float Voltage
37.5 Vdc
33 Vdc
39 Vdc
Battery Equalize
Equalize Voltage
43.2 Vdc
42 Vdc
51 Vdc
(Equalize)
Time
1.0 hours
0.0 hours
24.0 hours
Auxiliary Output
Aux Control
Auto
Off, Auto
or
On
Aux Mode
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed
, or
Remote
(Load Shed)
Enable Voltage
33 Vdc
30 Vdc
42 Vdc
(Gen Alert)
ON Voltage
33 Vdc
30 Vdc
42 Vdc
(Gen Alert ON)
Delay
4 minutes
0 minutes
240 minutes
(Gen Alert)
OFF Voltage
42 Vdc
36 Vdc
54 Vdc
(Gen Alert OFF)
Delay
9 minutes
0 minutes
240 minutes
(Vent Fan)
Enable Voltage
39 Vdc
30 Vdc
48 Vdc
(Vent Fan)
Off Period
5 minutes
0 minutes
30 minutes
(Divert DC or AC)
Enable Voltage
43.8 Vdc
36 Vdc
48 Vdc
(Divert DC or AC)
Off Delay
30 seconds
0 seconds
240 seconds
Inverter Stacking
Stack Mode
Master
1-2phase Master, Classic Slave, OB Slave L1,
OB Slave L2, 3phase Master, 3phase Slave
Power Save
Ranking
Master Adjust Only
0 0
7
Slave Adjust Only
1 1
15
Grid-Tie Sell
Grid Tie Enable
— Inoperative
Sell Voltage
— Inoperative
Grid Tie Window
— Inoperative
Calibrate
Input Voltage
25
-1 -3
1
Output Voltage
25
-1 -3
1
Battery Voltage
26
0.0 -0.6
0.6
25
These values represent an adjustable setting with a total range of 4 Vac. The default value of -1 means the calibration will subtract 1 volt from the measured value.
The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it. The result is also displayed.
26
These values represent an adjustable setting with a range of ± 0.6 Vdc from the measured value. The range of settings allows up to 0.6 volts to be either added or
subtracted from the measured value (in increments of 0.3 Vdc). The result is also displayed.