Specifications
50
900-0198-01-00 Rev A
Table 19
32-Volt Inverter Settings (MATE)
Field Item Default
Minimum
Maximum
Search
search sensitivity
(see page 14 for increments)
6
0
50
search pulse length
8 2 20
search pulse spacing
60 AC cycles
4 AC cycles
120 AC cycles
Input
ac transfer control
Grid
Grid
or
Gen
ac1/grid limit
28 Aac
5 Aac
30 Aac
ac2/gen limit
28 Aac
2 Aac
30 Aac
Inverter
low battery cut-out (LBCO)
27.7 Vdc
23.8 Vdc
31.7 Vdc
low battery cut-in (LBCI)
33 Vdc
29 Vdc
34.3 Vdc
adjust output voltage
120 Vac
110 Vac
125 Vac
Charger
charger limit
FX2532MT
12 Aac
0 Aac
14 Aac
VFX3232M
18 Aac
0 Aac
20 Aac
absorb voltage
38 Vdc
34.3 Vdc
42.2 Vdc
absorb time limit
1.0 hours
0.0 hours
24.0 hours
float voltage
35.9 Vdc
31.7 Vdc
39.6 Vdc
float time period
1.0 hours
0.0 hours
24.0 hours
refloat voltage
33 Vdc
29 Vdc
34.3 Vdc
equalization voltage
38 Vdc
37 Vdc
44.9 Vdc
equalization time period
1.0 hours
0.0 hours
24.0 hours
Grid
ac1/grid lower limit
108 Vac
40 Vac
115 Vac
ac1/grid upper limit
140 Vac
130 Vac
150 Vac
ac1/grid input limit
28 Aac
5 Aac
30 Aac
ac1/grid transfer delay
6 AC cycles
0 AC cycles
240 AC cycles
Generator
(Gen)
gen input connect delay
0.5 minutes
0.2 minutes
15 minutes
ac2/gen lower limit
108 Vac
40 Vac
115 Vac
ac2/gen upper limit
140 Vac
130 Vac
150 Vac
ac2/gen input limit
28 Aac
2 Aac
30 Aac
ac2/gen transfer delay
60 AC cycles
0 AC cycles
240 AC cycles
Auxiliary
(AUX)
aux output control
AUTO
ON, OFF
, or
AUTO
aux output function
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent
Fan, Fault, GenAlert, LoadShed
, or
Remote
genalert on voltage
29 Vdc
26.4 Vdc
37 Vdc
genalert on delay
4 minutes
0 minutes
240 minutes
genalert off set point
37 Vdc
31.7 Vdc
47.5 Vdc
genalert off delay
9 minutes
0 minutes
240 minutes
load shed off voltage
29 Vdc
26.4 Vdc
37 Vdc
vent fan on set point
34.3 Vdc
26.4 Vdc
42.2 Vdc
vent fan off period
5 minutes
0 minutes
30 minutes
diversion on voltage
38.5 Vdc
31.7 Vdc
42.2 Vdc
diversion off delay
30 seconds
0 seconds
240 seconds
Stacking
stack phase
Master
1-2ph Master, Classic Slave, OB Slave L1,
OB Slave L2, 3ph Master, 3ph Slave
Power Save
master adjust only
0 0 7
slave adjust only
1 1 15
Sell
sell re volts
— Inoperative
grid tie window
— Inoperative
grid tie authority
— Inoperative
Calibration
(Cal)
vac input adjustment
13
236 220 254
vac output adjustment
11
236 220 254
battery vdc adjustment
14
2 0 4
13
These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately 1 Vac.
The range of adjustment is 15 Vac above nominal and 17 Vac below nominal.
14
These values are in digital counts, not volts. One count equals 0.3 Vdc. The range of adjustment is 0.6 Vdc above or below nominal.