Ajan asetus
Changing the heating regulating c ircuit setting:
OK.
OK.
ESC.
Press the
button to move the cursor to the setting that you want to
change. Press
the
or
button to change the setting. Press
Exit with
Press
-
+
Press the
button to mov e cursor to "Settings". Press
OK.
SETTINGS
Browsing, making changes
6
H1 Select
Heating curve
Settings
Measurements
H1 Settings
Room temp.
Temp drop(w)
Min. limit
Max. limit
RoomCompens
Pre-increase
Autumn dry
Valve close
21.5
5
15
70
0
2
19
4.0
ESC - press to return to the previous display
Info button - gives operating instructions
Browse button - moves the cursor up and down
ESC
Press
ESC
until the display no longer changes.
You are then in the "Selection" display shown in the adjoining picture.
OPERATING INSTRUCTION:
Press
OK.
Group select button - not in use in EH201/L
H1
Outdoor
°C
SupplyTemp
°C
Selection
Automatic
-15
52
Explanation:
Room temperature setting, which user has
set.
The supply water temperature drop,
determined by the clock program or the
external home / away switch. (Room
compensation takes a desired drop in
room temperature into account)
Minimum allowed supply water temperature.
Maximum allowed supply water
temperature.
Room compensation ratio: If the room
temperature is different than what it is
set at, the room compensation corrects
the supply water temperature.
(Eg.) If the room compensation is 4 and
the room temperature has risen 1,5
above the setting, the regulator drops the
supply water temperature 6
(4x1,5
=6
).
°C
°C
°C
°C
Range:
5.0...45.0°C
0...35°C
5...95°C
15...125°C
0...7°C
Factory
settings:
21.5°C
0°C
15°C
70°C
4°C
Settings:
Room temp.
Temp drop
Min. limit
Max. limit
Room compens.
(w)
(supply water)
Attention!
During temp. drop period
regulator use the calculated
room temp. setting, which is
INFORMATION ABOUT SETTINGS:
80
65
50
35
20
20 0 -20 °C
Minimum limit
80
65
50
35
20
20 0 -20 °C
Maximum limit
Room sensor
(TMR) must
be connected (Meas.3 or
net).
Room temp. -
Temp drop(w)
Room compens.
In Ouman EH-201/L the regulator is controlled by many different
settings.
By browsing you can see which settings
you have in use.
Browsing and setting changes occur in the following way:
Settings are selected according to sensor connections
and relay control modes (e.g., is a relay controlling the oil burner or
pump or geothermal heating application or is the relay temperature
controlled (see p. 26 -28).