OUMAN EH-201/L
Instructions for setting the curve
OUMAN EH-201/L
80
65
50
35
20
20 0 -20 °C
EXAMPLES OF DIFFERENT HEATING SYSTEMS:
B) Floor heating
C) Preheating for air conditioning
If the room temperature drops in subzero weather, raise the curve setting at -20 C.
If the room temperature rises in subzero weather, lower the curve setting at -20 C.
If the room temp. feels chilly at zero degree weather, raise the curve setting at 0 C.
In this way you can set the regulating curve to meet the heating needs of your facility.
o
o
o
INSTRUCTION:
a) Normal radiator network
(factory setting)
80
65
50
35
20
20 0 -20 °C
80
65
50
35
20
20 0 -20 °C
H1 Curve:
0 = 44°C
+
-20 = 62°C
20 = 21°C
H1 Curve:
0 = 41°C
+
-20 = 58°C
20 = 18°C
H1 Curve:
0 = 27°C
+
-20 = 32°C
20 = 21°C
5
HOUSES WITH FLOOR HEATING:
Set the EH-201/L regulator's maximum limit b35 ... +40 C and
the minimum limit b20 ... +25 C.
In floor heating solutions it is important to make sure that exessively
hot water which could damage structures or surfaces doesn't ever get
into the network. A mechanical thermostat should be installed on a
supply water pipe which stops the circulation pump in case of
overheating. Ouman Oy keeps CO1A surface mounted thermostats in
stock that are suitable for this purpose. Set the thermostat at
40 ... 45 C.
o
o
o
Surface mounted
thermostat CO1A
AC 230V 15 (2,5) A
2
1
4
Pump
control
230 VAC
Pump control
Surface mounted thermostat’s C01A connection:
Model
Set point
Differential range
Temp. of cover,
range
°C
°C
o
C
CO1A
+20...+90
8
-35...+120
ATTENTION!
Wait a sufficient amount of time after the adjustment so the change has time to effect
the room temperature.
ESC - press to return to the previous display
Info button - gives operating instructions
Browse button - moves the cursor up and down
ESC
Group select button - not in use in EH201/L
HEA
TING
CUR
VE
H1
Curve:
(-20=
;
0=
;
+20=
)
58
41 19
KEYWORD:
Heating curve