OUMAN EH-201/L
ACTUATOR SELECTION
OUMAN EH-201/L
Press the
button to move the cursor to the actuator control mode that
you want to use.
Press
OK.
+
OK.
-
If you select the 3-point control mode, the regulator asks for the actuator's
running time. The running time indicates how many seconds go by if the
actuator drives a valve nonstop from a closed position to an open position.
Press the
or
button to set the time. Press
The
character indicates which control mode is being used.
Directions for entering the
maintenance mode are on page 21.
The control mode for regulating circuit actuator is selected in actuator
selection. Options are either 24 VAC 3-point control or DC voltage
control (0...10V or 2...10V). If relays 1 and 2 are free, they can be
utilized to implement 230VAC 3-point control. (first choose "230V
Actuator" for the relay control mode. (See pages 26 - 28)
H1
3-p./time
s
0-10V
2-10V
3-p230V
s
Actuator sel
150
150
VALVE ACTUATOR CONNECTION:
25
Open
Closed
3-point 24 VAC
0-10V
or
2-10V
71
72
73
74
75
3-point controlled
actuator (24VAC)
0...10V or 2...10V DC
controlled actuator
(24VAC)
3-point controlled actuator
(230 VAC)
Open
Closed
L
Actuator 230 VAC 3-point
Attention!
If "230V actuator" has been selected for
relays 1 and 2, 230VAC 3-point controlled actuator
can be connected to the regulator. Selection of
relay control modes is shown on pages 26 - 28.
H1 actuator
(control output M1)
24
VAC
H1 Maint mode
Tuning values
Settings
Trends
Actuator select
Relay1 control
ESC - press to return to the previous display
Info button - gives operating instructions
Browse button - moves the cursor up and down
ESC
Press the
button to move the cursor to “Actuator select”. Press
OK
.
H1 actuator
(control output M1)
Group select button - not in use in EH201/L
51
52
53
51
52
53
54
Ouman M31C150
Ouman M41A15