background image

INSTALLATION NOTES

FOR USE IN MOBILE HOMES

Diablo furnaces 15, 18 and 20 kW models are certified for “L” -shape
and “T”-shape shallow duct installation with model OFYOR-SO sub-base
in downflow applications when the supply air ducts pass through the
floor of the structure. Recommended size of a floor opening: 14¼” x 14¼”
(362 mm x 362 mm). The duct system must be designed so that the
external static pressure of the system does not exceed the maximum
external static pressure of 0.50” (13 mm) W.C. (125 Pa).

SHALLOW DUCT AREA REQUIREMENTS

Duct Depth

Duct Width

4” (102 mm)

16” (406 mm)

5” (127 mm)

13” (330 mm)

6” (152 mm)

10” (254 mm)

4

1. COLD AIR RETURN

The duct can be attached to either side, rear or the bottom of
the furnace.

For side return there are four 1½” (38 mm) knockouts which
can be removed and used as an outline for cutting a 18” x 18”
(457 mm x 457 mm) return air opening in the furnace left or
right side. Mount the filter frame to the furnace over the opening
with the open side of the frame facing front. Then attach the 
19” x 19” (483 mm x 483 mm) air duct to the flanges on the 
filter frame. For bottom mounting, remove the screws holding
the bottom plate to the furnace, discard the bottom plate and
attach the filter frame to the bottom flanges with the open side
of the frame facing front.

2.  ELECTRICAL WIRING - POWER SUPPLY

The furnaces are completely factory wired. From a separate
breaker, a two-wire plus ground supply wire is required. 
The ground conductor must be firmly attached to the ground lug
in the furnace and the supply wires to the terminal block in the
furnace.

NOTE:

If a OFR-120 kit will be used to supply an air cleaner 
and/or humidifier, a third (neutral) conductor must be 
brought into the furnace.

All wiring must conform to the latest editions of the Canadian
Electrical Code and local codes. Copper or aluminum wire of
the appropriate size may be used.

3. CONNECTING AND ADJUSTING 

THE LOW VOLTAGE THERMOSTAT
(Use only class 1 wires inside furnace compartments.)
Attach thermostat wires to the low voltage terminal 
connections located on the printed circuit board inside the 
furnace. Follow the diagrams supplied with the thermostat. As
a general guide, remember that the R & W terminals control
single stage heating; the R & Y terminals control cooling. Single
stage cooling uses “Y/Y2” as first and only stage.

Two-stage cooling uses “Y1” as first stage and “Y/Y2” as 
second stage. Make sure the thermostat is levelled on the wall
and in appropriate location as per instructions supplied with the
thermostat.

Because each installation is different an accurate reading of the
current draw should be made with an AC meter. Set the meter
at a 2 A range.
A. Set the anticipator at its highest setting.
B. Disconnect the “W1” thermostat wire from the furnace low 

voltage terminal connections.

C. Connect the AC meter between the “W1” terminal on the 

board and the loose “W1” wire.

D. Turn the thermostat up to start the furnace and allow it to 

run, with all elements on, for three or four minutes.

E. Read the current draw on the meter and reset the anticipator

to match the meter reading.

CAUTION

Before turning the furnace on, the heat anticipator in the 
thermostat must be properly set to prevent its failure and to
assure comfortable, economical heating.

Summary of Contents for Diablo OFR Series

Page 1: ...condition and to premature furnace failure thus voiding the warranty Do not block the combustion air openings in the furnace Any blockage will result in improper overheat situation and may result in...

Page 2: ...uired it will be indicated on the data label attached to the furnace 4 TEMPERATURE RISE Furnaces are shipped to operate at 0 20 5 mm W C 50 Pa external static pressure They are certified for operation...

Page 3: ...ing spring or fall you may require less rapid response when the thermostat calls for heat When Mild is selected it takes more time to bring all the elements online When Cold is selected the heating el...

Page 4: ...ly wires to the terminal block in the furnace NOTE If a OFR 120 kit will be used to supply an air cleaner and or humidifier a third neutral conductor must be brought into the furnace All wiring must c...

Page 5: ...lubricated for life and needs no oiling FILTERS Size is 20 x 20 x 1 508 mm x 508 mm x 25 mm Should be inspected and replaced when dirty Ordinarily replacement is required twice per heating season and...

Page 6: ...000 7 10940080 Element Assembly 5000 W 240 V 8 10940081 Element Assembly 4500 W 240 V 9 30274131 20 A Relay 10 30274132 30 A Relay 11 30280020 Manual Reset Limit 12 624665 Electronic Control PC Board...

Page 7: ...NC Line voltage wiring UL AWM 1015 1230 600V 105 C VW 1 12AWG CSA TEW 600V 105 C FT1 12AWG Low voltage wiring same ratings as high voltage except 18AWG Critical Characteristic 1 If any of the origina...

Page 8: ...COM NO HEAT 4 WHT 24Vdc PPL PPL BLK PPL BLK BLK SS TB2 NC Line voltage wiring UL AWM 1015 1230 600V 105 C VW 1 12AWG CSA TEW 600V 105 C FT1 12AWG Low voltage wiring same ratings as high voltage except...

Page 9: ...UTEC 1139 610 P2 3 P2 2 P2 1 P1 4 P1 3 P1 2 P1 1 24V regulated RLY PWR2 Heater Logic HEAT6 IN HEAT5 IN HEAT6 HEAT5 PNK GRY PNK PPL PNK PPL PNK BLK BLK BLK PPL TB2 SS NC Line voltage wiring UL AWM 101...

Page 10: ...efective 5 Must set thermostat much higher or lower than the desired house temperature Thermostat is not leveled or out of calibration 6 Not enough heat One or more defective elements or relays Season...

Reviews: