Operating Instructions PC-25 page 4 (10)

Water level- and backwash control :

Filter control PC-25

 

L1

 

NR-12-TRS-2

 

 

Water level control 

 

N

 

11

 

12

 

13

 

14

 

L1

 

N

 

11

 

12

 

13

 

14

 

EUROTRONIK-10

 

L1

 

N

 

2

 

3

 

4

 

5

 

L1

 

N

 

2

 

3

 

4

 

5

 

Backwash control

 

The factory-provided inserted bridge between clamps 

13

 and 

14

 must be removed on

connecting a level control NR-12-TRS-2. If no level control is connected, the bridge
between these clamps will have to be kept screwed in. In this case the clamps 

11

and 

12

 will remain unused. The clamps drive mains voltage!

The factory-provided inserted bridge between clamps 

3

 and 

5

 has to be removed on

connecting a EUROTRONIK-10. If no EUROTRONIK-10 is connected, the bridge
between these clamps have to be remained screwed in. In these case clamps 

2

 and

4

 will remain unused. The clamps drive mains voltage!

An opening of one of the contacts between clamps 

13 

and 

14

 or 

and 5 will result in

an immediate switching off of the filter pump, the dosing equipment and the heating.
The closing of one of the contacts between clamps 

2

 and 

4

 or 

11

 and 

12

 will cause a

forced switch on of the filter pump, whereas the heating and the dosing equipment
will be switched off.

Additional connecting possibilities:

Filter control PC-25

 

20

 

21

 

Dosing  equipment

 

(floating)

 

max. 230V / 4A

 

In the control unit there is a floating relay contact
between the clamps 20 and 21. This can for instance be
used to control the dosing equipment (the contact will be
closed during the filter operation).
This contact can be charged with a maximum of
230V/4A.

Temperature sensor:

 

Temperature 

sensor pool

 

30

 

31

 

sensor

 

Solar-

 

32

 

33

 

Filter control PC-25

 

  Immersion  shell

 

The pool temperature sensor is connected to the clamps 30 and 31. As a standard
the temperature sensor is delivered with cable length of 1.5m. If required, this can be
lengthened with a two-core cable (minimum diameter 0,5mm²) up to a maximum of
20m. It should be avoided to lay the sensor lead near power lines to exclude possible
disturbance.

Summary of Contents for 3100000430

Page 1: ...TRONIK 10 enable an upgrade of the filter control to an automatic filter and backwash control By using additional connecting terminals it is possible to connect accessory devices such as dosing equipm...

Page 2: ...housing it is absolutely necessary to switch the device to zero potential Electrical connection The electrical connection as well as adjustment and service work may only be carried out by accredited...

Page 3: ...ng PC 25 max 4A 22 23 heating 230V L1 N PC 25 heating 22 23 flow monitor L1 N or STB 400V L1 L2 L3 PC 25 U2 N 6 2 3 U3 actuator 230V Solar The floating relay contact between the clamps 22 and 23 can b...

Page 4: ...esult in an immediate switching off of the filter pump the dosing equipment and the heating The closing of one of the contacts between clamps 2 and 4 or 11 and 12 will cause a forced switch on of the...

Page 5: ...ect operating mode Pilot light operating mode Set time Interrogate soalr temperature Pilot light solar operation Pilot light heating Heating ON OFF LCD display Adjustment buttons LCD display 23 4 14 4...

Page 6: ...by the colour of the light green The temperature control is running the selected water temperature has been reached yellow The heating is running the selected temperature has not been reached yet red...

Page 7: ...ow be set 3 Press again the display will show 0 00 OFF 1 4 By pressing the and keys the requested off period can now be set 5 Press key again the display will show ON 2 6 Additional switching times ca...

Page 8: ...fuse on the circuit board The short circuit protection for the filter pump has to be ensured by customer provided pre fuses of max 16A Electronic motor protection 22 23 30 31 32 33 Heating Motor Water...

Page 9: ...nput 0 l Mains230V 1 N PE 11 12 13 14 4 7 6 5 8 U1 N N L1 Solenoid valve 230V Water level 3 N PE EUROTRONIK 10 Motor protect contact Filterpump temperature probe heating pump W Mains 400V chemical con...

Page 10: ...Operating Instructions PC 25 page 10 10...

Reviews: