Operating Instructions PC-25 page 3 (10)
Mains supply for use of a 230V-alternating current pump:
Pool-Control-25
winding
protection
1
M
W1
V1
U1
L3
L2
L1
N
WSK
FI-switch
max. B16A
pre-fusing
230V max. 8A
filter pump
mains 1/N/
230V 50Hz
25A/0,03A
N
The factory-provided inserted bridge between the two clamps named WSK, must be
removed, if connected to a pump with winding protective contact. If no connection is
carried out, it needs to be remained screwed in. The clamps lead mains supply!
For a proper operation of the electronic motor protection, the motor current has to be
driven via all three contact points of the filter control (clamp L2 and L3 and U1 and V1
bridged, pump connected to W1).
Connection of the heating:
Floating contact
(e.g. for the control
of the burner)
230V-heating (e.g.
circulating pump)
400V-heating (e.g. electric
heating)
Solar heating
PC-25
max. 4A
22
23
heating
floating
PC-25
max. 4A
22
23
heating 230V
L1
N
PC-25
heating
22
23
flow
monitor
L1
N
or STB
400V
L1
L2
L3
PC-25
U2
N
6
2
3
U3
actuator 230V
Solar-
The floating relay contact between the clamps 22 and 23 can be charged with a
maximum voltage of 230V with maximum 4A.
If the heating needs 230V, this required voltage can be obtained from the existing L1
clamps, which are sufficiently available in the PC-25. There are also clamps available
for the N-connection of the heating.
For the control of a 400V three-phase-current heating, an external contactor has to
be connected, that controls the heating.
In order to protect the heating against overheating, a flow monitor or a safety
thermostat can be inserted instead of a bridge between clamp L1 and 22.
For a solar-heated operation a
-solar-actuator 230V can be connected to the
clamps U2 and U3. With a solar operation, clamp U2 drives the mains voltage and
clamp U3 is dead circuit. If the solar heating is not controlled, clamp U2 will be dead
circuit and clamp U3 will drive the mains voltage. These contacts may be charged
with maximum 230V/1,5A.