background image

ENGINEERING STANDARDS 

  Rosedale Products Inc. 
  3730 west liberty Road 
  Ann Arbor, MI  48103 

 IOM 
 7_4_27 Model CR8.DOC 
 N:\IOM\ 

  

 

 Issue Date: 01MAY01 
 Revision: D 
 Revision Date: 24APR2015 

Specification No. 

7.4.27 

Page 1 of 14 

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

 

 

 
Rosedale Engineering Standards are the property of Rosedale Products, Inc.  A Rosedale Standard or copy thereof shall no be distributed (except with express approval of 
Rosedale Products, Inc.) to any individual or firm beyond the intended recipient firm or individual.  Firms of individuals acting contrary to the above may be subject to 
suit, ineligibility for continued or future employment, or removal from Rosedale’s “Approved Manufacturers and Specialty Contractors List”. 
 

 

 

 

INSTALLATION, OPERATION AND 

 

MAINTENANCE MANUAL

 

 

ROSEDALE PRODUCTS, INC. 

 

                           
 
 
 
 
 
 
 

MODEL CR8 

CR8302F*100PP*-PB (STANDARD BAG FILTER) 

CR81352F*100PP*-700 (STANDARD CARTRIDGE FILTER) 

CR81352F*100PP*-700-PB (CONVERTIBLE FILTER) 

 
 

Table of Contents

 

 

 
I. 

Installation of Bag Filter Vessel (Diagram A)...................................................................... 2 

 
II. 

Operation of Bag Filter Vessel............................................................................................... 4 

 
III. 

Installation of Cartridge Filter Vessel (Diagram B) ............................................................ 6 

 

IV. 

Operation of Bag Filter Vessel............................................................................................... 7 

 

V. 

Spare Parts List........................................................................................................................ 9 

 
VI. 

Pressure-Temperature Rating Chart ................................................................................... 10 

 
VII. 

Diagram A.............................................................................................................................. 11 

 

VIII.  Diagram B .............................................................................................................................. 12 

 

 

Summary of Contents for CR8 Series

Page 1: ... individual Firms of individuals acting contrary to the above may be subject to suit ineligibility for continued or future employment or removal from Rosedale s Approved Manufacturers and Specialty Contractors List INSTALLATION OPERATION AND MAINTENANCE MANUAL ROSEDALE PRODUCTS INC MODEL CR8 CR8302F 100PP PB STANDARD BAG FILTER CR81352F 100PP 700 STANDARD CARTRIDGE FILTER CR81352F 100PP 700 PB CON...

Page 2: ...lter bag and our latest series the Platinum 700 line of absolute rated cartridges Rosedale s Generation II Polypropylene Filter Vessels come complete with vent gauge and drain plugs hold down if required o rings and CPVC blind flange kit w full face gasket nuts bolts I Installation of Bag Filter Vessel Diagram A Please remove all shipping and crating materials carefully Be sure to remove the plugs...

Page 3: ...down the nuts diametrically opposite each other using a torque wrench Complete tightening should be accomplished in stages The final torque values are 20 30ft lbs Uniform stress across the flange will prevent leaky gaskets 6 The adjacent piping must be supported or anchored to eliminate excessive stress on the flange joint For side outlet configurations an optional Adjustable Tripod Leg Assembly o...

Page 4: ...ximately one half turn The application of process fluid to wet seal or lubricant will make it easier to install cover for a sufficient seal During the first several opening and closing cycles there may be some chafing of the cover threads This is normal and will cease as threads work into each other Your Rosedale Model CR8 is now ready for operation II Operation of Bag Filter Vessel Filter System ...

Page 5: ...lter media needs cleaning or replacement When it becomes necessary to clean or replace filter media follow the procedure outlined below 1 First close the flow from the inlet service line 2 Close the flow to the outlet service line In some applications closing flow to outlet is not required 3 Relieve the pressure from the filter unit 4 Drain housing sufficiently to access filter basket 5 Remove the...

Page 6: ...f the unit An optional Adjustable Tripod Leg Assembly is available for support of the filter unit See spare parts list for ordering information There are two 1 4 NPT ports on the shell and one 1 4 NPT port on the cover of the Model CR8 Filter unit These ports can remain plugged or used for pressure gauges sample ports vents or special fittings as your application requires Some installations requir...

Page 7: ... Manufacturers and Specialty Contractors List Insert the cartridge into the cartridge pedestal making sure the cartridge is fully seated into the pedestal When properly installed there will be an 1 8 clearance from the top of the 700 cartridge to the concave cover The cover will function as a hold down for the 700 cartridge Before replacing cover inspect cover seal gasket for damage replacing as n...

Page 8: ...roximately 25 of normal operational flow After filter unit is pressurized and vented slowly open outlet service line unit valve until completely open Complete opening of inlet service line until desired flow rate is reached Once the desired service flow has been established the filter will operate efficiently until dirty However under no circumstances should more than 25 PSI Differential Pressure ...

Page 9: ...ture employment or removal from Rosedale s Approved Manufacturers and Specialty Contractors List 7 Remove debris and sludge from inside the inlet portion of housing to avoid interference with cover seal or flow of fluid being filtered 8 Install new filter cartridge Make sure the cartridge is fully seated into the cartridge pedestal 10 Inspect cover gasket for cuts or other signs of failure and mak...

Page 10: ...needed Cover Seal CR8CG TEV TEV as needed 2 CR8 Cover 8 2004 PP 10 Glass filled w UV as needed 3 CR8 Vessel Body Only M8 1002 PP 10 Glass filled w UV as needed 4 CR8 Hold Down Assy 5 03246L PP as needed 5 CR8 Basket B 2003 PP as needed 6 1 4 NPT PP Plug 5 1817 PP as needed 7 3 4 NPT PP Plug 5 1222 PP as needed 8 Filter Bag See Order per application as needed 9 Filter Cartridge See Order per applic...

Page 11: ...water hammer etc is an important consideration for safe operation of the filter unit This is especially important at temperatures below 70 F Special Notice DO NOT USE THIS FILTER VESSEL PRODUCT WHEN ANY OPERATING TEMPERATURE CONDITION IS LESS THAN 40o F OR GREATER THAN 180o F Operating temperature conditions to consider when using the Rosedale CR8 filter vessel include but are not limited to the f...

Page 12: ...gineering Standards are the property of Rosedale Products Inc A Rosedale Standard or copy thereof shall no be distributed except with express approval of Rosedale Products Inc to any individual or firm beyond the intended recipient firm or individual Firms of individuals acting contrary to the above may be subject to suit ineligibility for continued or future employment or removal from Rosedale s ...

Page 13: ...gineering Standards are the property of Rosedale Products Inc A Rosedale Standard or copy thereof shall no be distributed except with express approval of Rosedale Products Inc to any individual or firm beyond the intended recipient firm or individual Firms of individuals acting contrary to the above may be subject to suit ineligibility for continued or future employment or removal from Rosedale s ...

Page 14: ...formance with any express warranty for a specific purpose Rosedale s only obligation and your exclusive remedy shall be to repair replace or refund the purchase price of such parts or products upon timely notification thereof and substantiation that the product has been stored maintained and used in accordance with Rosedale s written instructions EXCLUSIONS TO WARRANTY THIS WARRANTY IS EXCLUSIVE A...

Reviews: