Fireplace Installation and Operation Manual
__________________________________________________________________________ 61
DIMENSIONS OF HOT AIR OUTLET FRAME WITH ELBOW
DIMENSIONS OF HOT AIR OUTLET DECORATIVE GRILLE WITH ELBOW
The safety rules and installation procedures for both hot air gravity distribution kits (AC01375, AC01389)
are the following:
Minimum height*:
68" (1.7 m)
Minimum distance from ceiling: 12" (30 cm)
Maximum length:
10' (3m)
*The minimum height of the hot air ducting must be measured from the floor
to the top of the hot air
grilles.
The hot air grilles can be installed in the same room as the fireplace, or one or both of the grilles can be
installed in adjacent or upper rooms. Installing the ducts at different elevations will tend to exhaust more
heat out of the higher grilles.